<strong>USDT</strong> 2001 OPERATION<br />

ADVANCED MODE<br />

S etting mode – Press the selection key (yellow) for approximately two<br />

seconds to switch into the programming/setting mode. Software for<br />

solar water heating systems is stored in file P0. P1, P2, and P3 are program<br />

files for other applications. This manual covers only the solar water-heating<br />

program.<br />

Advancing – Press the selection key briefly to advance from one setting<br />

value to the next.<br />

Changing – Press Set-Up key once to increase the value. Hold it down to<br />

roll back to the lowest value after reaching the maximum value.<br />

Normal mode – To return to normal operating mode, press the selection<br />

key for two seconds while displaying P0. The system also returns to normal<br />

mode within one minute if no key is pressed.<br />

Software version number sequence<br />

Hysteresis curve for temperature differential control.<br />

H1x is for temperature difference and H2x is for maximum tank<br />

temperature curves with “x” as a corresponding value. Hysteresis<br />

curves (a lagging in the set-point) are variable and are a function of<br />

temperature. For example H14 (actual factory setting) means that the<br />

hysteresis of the maximum temperature is 4 o F at 64 o F (pump is on at<br />

60 o F and off at 64 o F) or 8 o F at 128 o F.<br />

9<br />