<strong>USDT</strong> 2001 OPERATION<br />
ADVANCED MODE<br />
S etting mode – Press the selection key (yellow) for approximately two<br />
seconds to switch into the programming/setting mode. Software for<br />
solar water heating systems is stored in file P0. P1, P2, and P3 are program<br />
files for other applications. This manual covers only the solar water-heating<br />
program.<br />
Advancing – Press the selection key briefly to advance from one setting<br />
value to the next.<br />
Changing – Press Set-Up key once to increase the value. Hold it down to<br />
roll back to the lowest value after reaching the maximum value.<br />
Normal mode – To return to normal operating mode, press the selection<br />
key for two seconds while displaying P0. The system also returns to normal<br />
mode within one minute if no key is pressed.<br />
Software version number sequence<br />
Hysteresis curve for temperature differential control.<br />
H1x is for temperature difference and H2x is for maximum tank<br />
temperature curves with “x” as a corresponding value. Hysteresis<br />
curves (a lagging in the set-point) are variable and are a function of<br />
temperature. For example H14 (actual factory setting) means that the<br />
hysteresis of the maximum temperature is 4 o F at 64 o F (pump is on at<br />
60 o F and off at 64 o F) or 8 o F at 128 o F.<br />
9<br />
Thermo <strong>Technologies</strong>