Dy.CSTE/Con/ IZN/02 of 2011 <strong>North</strong> <strong>Eastern</strong> <strong>Railway</strong><br />
3.12.18 The conditions of the cable shall be visually inspected through out its length and in<br />
case any damage or defect is noticed, the trench shall not be filled up until the<br />
engineer's representative in notified to examine and authorize filling of the trench.<br />
3.12.19 MINIMUM BENDING RADIUS: Cable should always be bent ( or straightened)<br />
slowly; They should never be bent to small radius while handling. The minimum safe<br />
vending radius for telecommunication cables should be 30 times the diameter of the<br />
cable but wherever possible larger radius should be used.<br />
3.13 CABLE RESERVE:<br />
a) At the following locations, it will necessary to provide reserve cable for future<br />
possible use.<br />
(i) Where a change to cable line is expected, the reserve to be allowed<br />
depends on circumstances.<br />
(ii) In freshly banked soil to allow for slipping of the bank an allowance of<br />
30 cm. should be provided for every 10M of trench (3%).The cable<br />
should be laid in a sinuous form.<br />
(iii) Near roadways, buildings and culverts reserve of 5 M should be allowed<br />
at drum end .<br />
(iv) On each side of girder bridges a reserve of 10M should be left.<br />
(v) Where remodeling works on culverts, bridges and track doubling work<br />
are going on, it may be necessary to kept loops of cable as an extra<br />
reserve pending finalization of its future route.<br />
(vi) At the cable hut a loop of 10M in the cable pit & At every joint a loop<br />
of 10M on either side.<br />
FRP CABLE ROUTE MARKER:<br />
3.14.1 The FRP CABLE ROUTE MARKERS shall normally be provided at the<br />
distance of every 100 Meter on the cable route and also at places or corners<br />
wherever the route of the cable changes, as per direction of site engineer. The<br />
cable joint markers shall be provided at all types of cable joints, as per<br />
direction of site engineer. The cable route makers and cable joint markers shall<br />
be provided & installed as per Drg.No.JBP/ S&T/C/083 & as per RDSO<br />
specification No.RDSO/SPN/151/1997 with latest amendments.<br />
3.14.1 The FRP CABLE ROUTE MARKERS shall normally be provided at the<br />
distance of every 100 Meter on the cable route and also at places or corners<br />
wherever the route of the cable changes, as per direction of site engineer. The<br />
cable joint markers shall be provided at all types of cable joints, as per<br />
direction of site engineer. The cable route makers and cable joint markers shall<br />
be provided & installed as per Drg.No.JBP/ S&T/C/083 & as per RDSO<br />
specification No.RDSO/SPN/151/1997 with latest amendments.<br />
3.14.2 TEC APPROVED ELECTRONIC MARKERS shall normally be provided at a<br />
distance of every 100 M on the cable route and also at places or corners<br />
wherever the route of the cable changes, as per direction of site engineer. The<br />
inter spacing between the adjascent FRP CABLE ROUTE MARKER &<br />
Signature of Tenderer(s)<br />
Date…………………<br />