Connection with FVR-E11S series<br />
The pin assignment of FVR-E11S series differs from that of FRENIC series.<br />
Therefore, it may be impossible to access the communications system to which<br />
FVR-E11S is connected. The signal change switch (SW10) equalize the signal<br />
assignment with that of FVR-E11S series, which makes it easy to connect with the<br />
communications system. When SW10 switch is set to "2", the functions are<br />
assigned to the pins as shown in the table below.<br />
Pin No. Signal name Description Remarks<br />
1, 6, 7, 8 NC Unused −<br />
2 SD<br />
Communications cable shielded<br />
terminal<br />
3 DX- <strong>RS</strong>-<strong>485</strong> communications data (-)<br />
terminal<br />
4 DX+ <strong>RS</strong>-<strong>485</strong> communications data (+)<br />
terminal<br />
5 NC<br />
Unused<br />
2-6<br />
Terminal for relaying the shield<br />
of the shielded cable. The 2nd<br />
terminals of the two RJ-45<br />
connectors are internally<br />
connected with each other.<br />
Negative terminal for <strong>RS</strong>-<strong>485</strong><br />
communications data<br />
Positive terminal for <strong>RS</strong>-<strong>485</strong><br />
communications data<br />
The 5th terminals of the two<br />
RJ-45 connectors are<br />
internally connected with each<br />
other.<br />
* For comparison of pin assignment between FRENIC series and FVR-E11S series, see "Table<br />
2.3. in 2.2.2 Caution [1] RJ-45 connector (modular jack) pin layout. "<br />
For the arrangement of the signal change switch (SW10), see "Figure 2.6 (e) in 2.2.2 Cautions<br />
[2] About terminating resistors."