2.3.3 How to switch communications enabled/disabled<br />

To issue a frequency setting or operation command through communications to control the<br />

inverter, select "Through <strong>RS</strong>-<strong>485</strong> communications" by function code H30: link function<br />

(operation selection).<br />

In addition, when switching control through communications with control from the terminal block<br />

(frequency setting from terminal [12], operation command from terminal [FWD] and so on) to<br />

switch remote operations with operations on the inverter body, assign "link operation selection"<br />

(data = 24: "LE") to the function code related to the digital input terminal (one of E01-E05:<br />

terminals [X1] to [X5], E98: terminal [FWD], or E99: terminal [REV]). (FRENIC-Mini does not<br />

support E04, E05, [X4], and [X5].) Control can be switched by the terminal to which "link<br />

operation selection" (data = 24: "LE") is assigned.<br />

Communications automatically becomes valid when link operation selection is not assigned to<br />

any digital input terminal.<br />

Table 2.5 Digital input terminal settings and communications statuses<br />

Input terminal Status<br />

OFF Communications invalid<br />

ON (short-circuited to Communications valid<br />

the terminal [CM])<br />

- Via-communications command data and operation data must be rewritten from the<br />

host (controller) because the memory is initialized when the power is turned ON.<br />

- Although command data and operation data can be written even if communications<br />

is invalid, they will not be validated because the switch is made invalid by link<br />

operation selection. If communications is made valid with no operation data written<br />

(operation command OFF, frequency setting = 0Hz) during operation, the running<br />

motor decelerates to a stop and may exert impact on the load depending on the set<br />

deceleration time. Operation can be switched without causing impact to the load by<br />

setting data in communications invalid mode in advance and then switching the<br />

mode to valid.<br />

- If negative logic is set as Link enable (data 1024), the logical value corresponding to<br />

the ON/OFF status of the command "LE" will be reversed.<br />

- FRENIC-Eco/Multi/MEGA has the field bus option other than <strong>RS</strong>-<strong>485</strong><br />

communications. The field bus option is handled prior to <strong>RS</strong>-<strong>485</strong> communications<br />

depending on the setting of it in some cases. For details, see the function code "y98<br />

Bus function (function selection)" of each inverter type.<br />

2-20