2.3 Switching to Communications<br />

2.3.1 Functions for the switching<br />

Figure 2.9 below shows a block diagram via communications for frequency setting and operation<br />

commands.<br />

This block diagram indicates only the base of the switching section, and some settings may be<br />

given higher priority than the blocks shown in this diagram or details may be different due to<br />

functional expansion and so on. For details, see the <strong>User's</strong> <strong>Manual</strong> of each inverter model.<br />

(Chapter 4 for FRENIC-Mini/Eco/Multi, and Chapter 6 for FRENIC-MEGA)<br />

Operation commands herein include digital input signals via communications.<br />

According to the setting of function code H30 link function (operation selection), the command<br />

system when communications is valid is selected.<br />

Even if digital input is set to link enable (LE), when the link becomes invalid ("LE" = OFF), the<br />

command system switches from communications to other settings including digital input signal.<br />

In short, the frequency setting, forward operation command, and X1 signal in Figure 2.9 switch<br />

from communications dedicated function codes S01, S05, and S06 to terminals [12], [FWD],<br />

and [X1], respectively.<br />

Function code data can be read and written through communications regardless of the setting<br />

function code H30 (link function (operation selection)).<br />

Set<br />

frequency<br />

Host<br />

Forward operation<br />

command<br />

Digital input<br />

Digital input (link<br />

operation<br />

selection)<br />

Communications<br />

Set frequency for<br />

communications<br />

Set frequency for<br />

communications<br />

Operation command<br />

Terminal FWD<br />

(function selection)<br />

Operation command<br />

Turned<br />

ON at<br />

98<br />

Treminal REV<br />

(function selection)<br />

Operation command<br />

Operation command 1<br />

Turned<br />

ON at<br />

98<br />

computing unit Table of truth values of SO6 (bit<br />

13, bit 14)) computing unit<br />

*1 The code y98 (bus function: operation selection) is not available in FRENIC-Mini.<br />

Figure 2.9 Operation command block diagram via communications<br />

2-18<br />

to<br />

Link function<br />

Bus function*1 Link function<br />

for aid<br />

Link function<br />

Bus function*1 Link function<br />

for aid<br />

0.1<br />

to<br />

2,3<br />

-: Not assigned<br />

(The value of the assigned bit will be<br />

Link function<br />

Link function<br />

Bus function*1 for aid<br />

0.1<br />

to<br />

2,3<br />

Depends on the set function.<br />

Communications/Termin<br />

al block switching<br />

Frequency<br />

setting<br />

Forward<br />

operation<br />

X1 signal

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!