2.4 Making <strong>RS</strong>-<strong>485</strong>-related Settings<br />

2.4.1 Link function (<strong>RS</strong>-<strong>485</strong> setting)<br />

Use function codes (y01 to y10 and y11 to y20) to make settings for <strong>RS</strong>-<strong>485</strong> communications<br />

functions. Use the codes y01 to 10 for port 1 and the codes y11 to 20 for port 2.<br />

Station address (y01, y11)<br />

Set a station address for <strong>RS</strong>-<strong>485</strong> communications. The setting range depends on the protocol.<br />

Table 2.7 <strong>RS</strong>-<strong>485</strong> setting (station addresses)<br />

Protocol Range Broadcast<br />

Modbus RTU protocol 1 to 247 0<br />

Protocol for loader commands 1 to 255 −<br />

<strong>Fuji</strong> general-purpose inverter protocol 1 to 31 99<br />

- No response is expected if an address number out of the specified range is set.<br />

- Match the station address with that of the personal computer when FRENIC Loader<br />

is connected.<br />

Operation made selection when an error occurs (y02, y12)<br />

Set the operation performed when an <strong>RS</strong>-<strong>485</strong> communications error occurs.<br />

<strong>RS</strong>-<strong>485</strong> communications errors are logical errors such as an address error, parity error, or<br />

framing error, transmission error, and communications disconnection error set by y08 and y18.<br />

In any case, error is detected only while the inverter is running in the link operation made for<br />

both the operation command and frequency setting. If neither the operation command nor<br />

frequency setting is sent through <strong>RS</strong>-<strong>485</strong> communications or the inverter is not running, error is<br />

ignored.<br />

Table 2.8 <strong>RS</strong>-<strong>485</strong> setting (operations when an error has occurred)<br />

y02, y12 data Function<br />

0 Indicates an <strong>RS</strong>-<strong>485</strong> communications error (er8 for port 1 and erp for port<br />

2), and stops operation immediately (alarm stop).<br />

1 Runs during the time set on the error processing timer (y03, y13), and then<br />

displays an <strong>RS</strong>-<strong>485</strong> communications error (er8 for port 1 and erp for port 2)<br />

and stops operation (alarm stop).<br />

2 Runs during the time set on the error processing timer (y03, y13). If<br />

communications are recovered, continues operation. Otherwise, displays an<br />

<strong>RS</strong>-<strong>485</strong> communications error (er8 for port 1 and erp for port 2) and stops<br />

operation (alarm stop).<br />

3 Continues operation even after a communications error has occurred.<br />

Timer for y02 and y12 (y03, y13)<br />

Set a timer for error detection.<br />

It is judged as an error that the response to a request is not received within time set because of<br />

no response of the other end and so on. See the section of "Communications disconnection<br />

detection time (y08, y18)."<br />

- Data input range: 0.0 to 60.0 (s)<br />

2-22