2.4 Making <strong>RS</strong>-<strong>485</strong>-related Settings<br />
2.4.1 Link function (<strong>RS</strong>-<strong>485</strong> setting)<br />
Use function codes (y01 to y10 and y11 to y20) to make settings for <strong>RS</strong>-<strong>485</strong> communications<br />
functions. Use the codes y01 to 10 for port 1 and the codes y11 to 20 for port 2.<br />
Station address (y01, y11)<br />
Set a station address for <strong>RS</strong>-<strong>485</strong> communications. The setting range depends on the protocol.<br />
Table 2.7 <strong>RS</strong>-<strong>485</strong> setting (station addresses)<br />
Protocol Range Broadcast<br />
Modbus RTU protocol 1 to 247 0<br />
Protocol for loader commands 1 to 255 −<br />
<strong>Fuji</strong> general-purpose inverter protocol 1 to 31 99<br />
- No response is expected if an address number out of the specified range is set.<br />
- Match the station address with that of the personal computer when FRENIC Loader<br />
is connected.<br />
Operation made selection when an error occurs (y02, y12)<br />
Set the operation performed when an <strong>RS</strong>-<strong>485</strong> communications error occurs.<br />
<strong>RS</strong>-<strong>485</strong> communications errors are logical errors such as an address error, parity error, or<br />
framing error, transmission error, and communications disconnection error set by y08 and y18.<br />
In any case, error is detected only while the inverter is running in the link operation made for<br />
both the operation command and frequency setting. If neither the operation command nor<br />
frequency setting is sent through <strong>RS</strong>-<strong>485</strong> communications or the inverter is not running, error is<br />
ignored.<br />
Table 2.8 <strong>RS</strong>-<strong>485</strong> setting (operations when an error has occurred)<br />
y02, y12 data Function<br />
0 Indicates an <strong>RS</strong>-<strong>485</strong> communications error (er8 for port 1 and erp for port<br />
2), and stops operation immediately (alarm stop).<br />
1 Runs during the time set on the error processing timer (y03, y13), and then<br />
displays an <strong>RS</strong>-<strong>485</strong> communications error (er8 for port 1 and erp for port 2)<br />
and stops operation (alarm stop).<br />
2 Runs during the time set on the error processing timer (y03, y13). If<br />
communications are recovered, continues operation. Otherwise, displays an<br />
<strong>RS</strong>-<strong>485</strong> communications error (er8 for port 1 and erp for port 2) and stops<br />
operation (alarm stop).<br />
3 Continues operation even after a communications error has occurred.<br />
Timer for y02 and y12 (y03, y13)<br />
Set a timer for error detection.<br />
It is judged as an error that the response to a request is not received within time set because of<br />
no response of the other end and so on. See the section of "Communications disconnection<br />
detection time (y08, y18)."<br />
- Data input range: 0.0 to 60.0 (s)<br />