Troubleshooting, Cont.<br />
I. Excess or Insufficient Output Pressure<br />
• Inspect the control hoses, connectors, shuttle valves <strong>and</strong><br />
adapters. Replace as necessary.<br />
• Rotate the adjustment screw atop of the pilot valve. Rotate<br />
clockwise to increase pressure or counterclockwise to reduce<br />
pressure as necessary.<br />
• Remove <strong>and</strong> clean the finger strainer. Replace if necessary.<br />
• If this fails to balance the pressure, try the following procedure:<br />
- Unscrew <strong>and</strong> remove the throttle housing (12) at the<br />
bottom of the pilot valve.<br />
- Remove the throttle pin (14) from inside the housing.<br />
- Wrap the throttle pin (14) with Teflon tape <strong>and</strong> re-insert<br />
it into the housing.<br />
- Re-insert <strong>and</strong> tighten the throttle housing into the pilot<br />
• Replace the pilot valve.<br />
J. Excess or Insufficient Input Pressure<br />
• Inspect the control hoses, connectors, shuttle valves <strong>and</strong> adapters. Tighten <strong>and</strong> replace as<br />
necessary.<br />
• Remove <strong>and</strong> clean the finger strainer. Replace if necessary.<br />
• Repair or replace the pilot valve.<br />
K. Excess or Insufficient Flow Rate<br />
• Inspect the control hoses, connectors, shuttle valves <strong>and</strong><br />
adapters.<br />
• Tighten <strong>and</strong> replace as necessary.<br />
• Rotate the adjustment screw on the top of the pilot valve.<br />
Rotate clockwise to increase flow rate or counterclockwise<br />
to reduce the flow rate as necessary.<br />
• Clean <strong>and</strong> check the orifice <strong>and</strong> gaskets. Replace as<br />
necessary.<br />
• Remove <strong>and</strong> clean the finger strainer. Replace if necessary.<br />
• If this fails to balance the pressure, try the following<br />
procedure:<br />
- Unscrew <strong>and</strong> remove the throttle housing (12) at the<br />
bottom of the pilot valve.<br />
- Remove the throttle pin (14) from inside the<br />
housing.<br />
- Wrap the throttle pin (14) with Teflon tape <strong>and</strong><br />
re-insert it into the pilot valve.<br />
• Replace the pilot valve.<br />
22 • <strong>Hydrometers</strong> <strong>Operation</strong> <strong>and</strong> <strong>Maintenance</strong> <strong>Manual</strong>