<strong>Maintenance</strong> 1½” - 8” <strong>Hydrometers</strong>, Cont.<br />

FINGER STRAINER CLEANING AND REPLACEMENT<br />

It is not necessary to remove the hydrometer from the pipeline or to disassemble it in order to<br />

perform this procedure.<br />

To Remove the Finger Strainer:<br />

• Locate the inlet connection on the hydrometer body.<br />

• Remove the angle nipples <strong>and</strong> other connection devices.<br />

• Turn the nut counter-clockwise to loosen the finger strainer.<br />

• Gently pull the finger strainer out.<br />

• Clean or replace as necessary.<br />

To Replace the Finger Strainer:<br />

• Insert the finger strainer into the inlet connection <strong>and</strong> turn clockwise to tighten.<br />

• Apply Teflon tape or similar material to seal the connections.<br />

• Re-install the angle nipples <strong>and</strong> other connection devices.<br />

REGISTER ASSEMBLY REMOVAL<br />

AND REPLACEMENT<br />

It is not necessary to disassemble the hydrometer to perform this procedure.<br />

Removal:<br />

• Remove the reed switch transducer (4) from<br />

the register dial.<br />

Gently turn <strong>and</strong> pull the switch (4) upward to<br />

release it.<br />

• Close the register cover (1).<br />

• Using a large pipe wrench, turn the register<br />

cover assembly (1, 2) counterclockwise until<br />

you can remove it from the hydrometer cover<br />

(12).<br />

• Remove <strong>and</strong> set aside the sliding ring (3).<br />

• Lift the register assembly (5) out of the<br />

hydrometer body.<br />

• Remove the register o-ring (6) <strong>and</strong> the adapter<br />

ring (7) from<br />

the register.<br />

• Inspect <strong>and</strong> replace as necessary.<br />

Replacement:<br />

• Close the register cover (1).<br />

• Place the register o-ring (6) around the register assembly. Insert the register assembly into<br />

the adapter ring (7) <strong>and</strong> place them inside the hydrometer cover (12).<br />

• Replace the sliding ring (3) over the register assembly.<br />

• Replace the register cover assembly (1, 2) over the register. Turn it clockwise to tighten.<br />

• Insert the reed switch (4) into its hole in the register dial. Gently turn the reed switch until<br />

it is fully seated.<br />

<strong>Hydrometers</strong> <strong>Operation</strong> <strong>and</strong> <strong>Maintenance</strong> <strong>Manual</strong> • 25