<strong>Maintenance</strong> 1½” - 8” <strong>Hydrometers</strong>, Cont.<br />
FINGER STRAINER CLEANING AND REPLACEMENT<br />
It is not necessary to remove the hydrometer from the pipeline or to disassemble it in order to<br />
perform this procedure.<br />
To Remove the Finger Strainer:<br />
• Locate the inlet connection on the hydrometer body.<br />
• Remove the angle nipples <strong>and</strong> other connection devices.<br />
• Turn the nut counter-clockwise to loosen the finger strainer.<br />
• Gently pull the finger strainer out.<br />
• Clean or replace as necessary.<br />
To Replace the Finger Strainer:<br />
• Insert the finger strainer into the inlet connection <strong>and</strong> turn clockwise to tighten.<br />
• Apply Teflon tape or similar material to seal the connections.<br />
• Re-install the angle nipples <strong>and</strong> other connection devices.<br />
REGISTER ASSEMBLY REMOVAL<br />
AND REPLACEMENT<br />
It is not necessary to disassemble the hydrometer to perform this procedure.<br />
Removal:<br />
• Remove the reed switch transducer (4) from<br />
the register dial.<br />
Gently turn <strong>and</strong> pull the switch (4) upward to<br />
release it.<br />
• Close the register cover (1).<br />
• Using a large pipe wrench, turn the register<br />
cover assembly (1, 2) counterclockwise until<br />
you can remove it from the hydrometer cover<br />
(12).<br />
• Remove <strong>and</strong> set aside the sliding ring (3).<br />
• Lift the register assembly (5) out of the<br />
hydrometer body.<br />
• Remove the register o-ring (6) <strong>and</strong> the adapter<br />
ring (7) from<br />
the register.<br />
• Inspect <strong>and</strong> replace as necessary.<br />
Replacement:<br />
• Close the register cover (1).<br />
• Place the register o-ring (6) around the register assembly. Insert the register assembly into<br />
the adapter ring (7) <strong>and</strong> place them inside the hydrometer cover (12).<br />
• Replace the sliding ring (3) over the register assembly.<br />
• Replace the register cover assembly (1, 2) over the register. Turn it clockwise to tighten.<br />
• Insert the reed switch (4) into its hole in the register dial. Gently turn the reed switch until<br />
it is fully seated.<br />
<strong>Hydrometers</strong> <strong>Operation</strong> <strong>and</strong> <strong>Maintenance</strong> <strong>Manual</strong> • 25