Performance charts.<br />
daPa<br />
80<br />
60<br />
40<br />
20<br />
0<br />
C.75 GX 507 p20/25<br />
mbar<br />
0<br />
100 300 500 700 900 1100 kW<br />
140 335 750<br />
C.75 GX 507/8 p37-148-300<br />
daPa<br />
mbar<br />
8<br />
6<br />
4<br />
2<br />
daPa<br />
80<br />
60<br />
40<br />
20<br />
0<br />
C.100 GX 507 p20/25<br />
mbar<br />
0<br />
100 300 500 700 900 1100 kW<br />
170 520 1040<br />
C.100 GX 507/8 p37-148-300<br />
daPa<br />
mbar<br />
8<br />
6<br />
4<br />
2<br />
Packing.<br />
The burner is delivered in three<br />
separately packaged palettes weighing<br />
between 74 and 79kg depending on<br />
the model.<br />
• Burner body:<br />
- Integrated electrical bearing plate,<br />
- Boiler plate,<br />
- Documentation, including:<br />
- operating instructions,<br />
- electrical and hydraulic<br />
diagrams,<br />
- certificate of guarantee.<br />
• Combustion head:<br />
- front boiler attachment, a set of<br />
fasteners.<br />
• Gas rack:<br />
- valve set and collector.<br />
80<br />
8<br />
80<br />
8<br />
60<br />
6<br />
60<br />
6<br />
40<br />
4<br />
40<br />
4<br />
Front panel boring.<br />
20<br />
2<br />
20<br />
2<br />
0<br />
0<br />
100 300 500 700 900 1100 kW<br />
140 335 750<br />
Output levels.<br />
0<br />
0<br />
100 300 500 700 900 1100 kW<br />
170 530 1040<br />
Ø 260max<br />
Ø 195<br />
C.75 49 AQ 0924 C.100 49 AQ 0925<br />
20/25 37/148 300 20/25 37/148 300<br />
Output KW mbar mbar mbar mbar mbar mbar<br />
min max min max min max min max<br />
Burner (kW) 335 680 750 750 530 720 1040 1040<br />
Min. 1 st startup (kW) 140 — — — 170 — — —<br />
Boiler (kW) 310 625 690 690 490 665 960 960<br />
In bold, recommended ø.<br />
Bulk and dimensions.<br />
valve<br />
A minimum of 0.80m must be allowed<br />
on either side of the burner for<br />
maintenance purposes.<br />
Ventilation in the boiler room.<br />
1.2m 3 of new air is required for every<br />
kWh produced by the burner.<br />
Gas rack.<br />
The rack can only be installed<br />
horizontally, to the right or left.<br />
Note:<br />
The burner may be installed with the<br />
casing at the top or bottom.