<strong>Low</strong> <strong>NOx</strong><br />
Output adjustment.<br />
Operation.<br />
After startup (which uses approx. 15%<br />
of the normal flow), the thermal output<br />
progressively increases through two<br />
different flows.<br />
These can be adjusted to:<br />
- “Full” or “off”: progressive output<br />
increase (between 20 and 30<br />
seconds).<br />
The equipment benefits from all the<br />
combustion control of the AGP ®<br />
system.<br />
- “Full” or “low”: this type of setting<br />
offers not only the advantages of the<br />
AGP ® system, but saves energy by<br />
operating at reduced power.<br />
- “Modulating”: the power can be<br />
adapted to requirements. High<br />
performance installations offer a<br />
wide range of options:<br />
- adjustment of generator<br />
temperature to suit atmospheric<br />
conditions or to an existing setting.<br />
- adjustment to a required constant or<br />
variable temperature,<br />
- parallel adjustment of several<br />
generators to suit a decreasing or<br />
constant temperature,<br />
- cascade burner, pump and boiler<br />
adjustment for a temperature that is<br />
constant, variable, etc…<br />
Setting connection.<br />
- Connect terminals 84 and 85 for “full”<br />
flow or “off”.<br />
- Use the three-wire contact instruments<br />
for a “full” or “low” flow controlled by a<br />
thermostat or pressure switch.<br />
- A kit is provided with a prewired fusebase<br />
for a “Modulating” flow using an<br />
RC.40 or RC.6170 regulator. The<br />
control system is mounted on the<br />
control panel in the position reserved<br />
for this purpose.<br />
Using a standard electronic regulator<br />
(PID): this type of regulator is mounted<br />
in the standardized position reserved<br />
for this purpose (48 x 48 or 48 x 96).<br />
Note: The RC.40 or RC.6170 and the<br />
“alarm” output on certain regulators<br />
control operation.<br />
Imprimé en Italie par Musumeci Industrie Grafiche S.p.A.<br />
We reserve the right to upgrade equipment where required.<br />
10/2003 - EN