149<br />

fed from a sectionalized power plant,<br />

the distribution voltages in the individual<br />

parts must be held at the same<br />

value to within very close limits.<br />

The requirements <strong>set</strong> by LM Ericsson<br />

are that the difference between voltages<br />

in the negative conductor at two<br />

arbitrarily selected rack fuses must not<br />

exceed 0.8 V and that the voltage difference<br />

at two corresponding points in<br />

the positive conductor must not exceed<br />

0.6 V.<br />

Since the major part of this tolerance<br />

is used to cover the differences in<br />

voltage drop in the distribution cables,<br />

the permissible difference between different<br />

distribution racks constitutes<br />

only a small fraction of the values<br />

given above (