2. Installation Output Circuits<br />
Output Circuits<br />
Notification Appliance Circuits<br />
The control panel provides four Notification Appliance Circuits (two Style Y or Z and two Style Y only).<br />
Each circuit is capable of 1.5 amps of current. Total current drawn from all four circuits cannot exceed<br />
2.25 amps. NACs are supervised and power-limited.<br />
Note: Refer to the Device Compatibility Document for suitable devices.<br />
For details on how jumper configurations affect panel functions see Table 1, “Jumper Configuration Table”<br />
on page 24.<br />
• For DIP switch configuration, see "Setting Mode of Operation" on page 31.<br />
• For non-silenceable service on Initiating Zone #1, see "Non-Silenceable Service" on page 36.<br />
• Unused circuits must be connected with a dummy load as shown.<br />
Polarized<br />
Bell<br />
Style Z<br />
(Class A)<br />
Style Y<br />
(Class B)<br />
4.7K, 1/2-Watt ELR<br />
(PN 71252)<br />
Polarized<br />
Strobe<br />
Unused Style Y Circuit<br />
(4.7K, 1/4-Watt ELR)<br />
Polarized<br />
Horn<br />
TB2<br />
<strong>MS</strong>44-nac.cdr<br />
Figure 9 Notification Appliance Circuits<br />
22 <strong>MS</strong>-<strong>4424</strong> <strong>Instruction</strong> <strong>Manual</strong> PN 15153:G1 10/22/02