3. System Operation Last Event Recall<br />

Last Event Recall<br />

Last Event Recall allows the user to display the previous panel status. The Last Event Recall makes use<br />

of the four panel switches as follows:<br />

1. Press and hold in the TONE SILENCE switch.<br />

2. With the TONE SILENCE switch held in, press (in sequence) the SYSTEM RESET switch, the<br />

ALARM ACTIVATE switch, and then the ALARM SILENCE switch.<br />

3. LEDs will light to indicate the last event recorded in the panel’s buffer.<br />

4. Release the TONE SILENCE switch to return to normal operation.<br />

To clear the Last Event buffer, press SYSTEM RESET twice.<br />

Non-Silenceable Service<br />

Initiating Zone #1 can be programmed as non-silenceable by following these steps:<br />

1. Press and hold in the TONE SILENCE switch.<br />

2. With the TONE SILENCE switch held in, press in sequence the ALARM SILENCE switch, then<br />

the ALARM ACTIVATE switch, and finally the ALARM SILENCE switch again.<br />

3. Release the TONE SILENCE switch.<br />

Note: If both primary and secondary power sources are removed from the system, these settings will be lost. When<br />

power is restored, Initiating Zone #1 will default to silenceable operation.<br />

Sprinkler Supervisory Tracking<br />

System Events<br />

The Initiating Device Circuit for sprinkler supervisory zone can be programmed for tracking operation;<br />

latching operation is the default setting. Canadian regulations require latching operation.<br />

1. Press and hold in the TONE SILENCE switch.<br />

2. With the TONE SILENCE switch held in, press in sequence the ALARM SILENCE switch, then<br />

the ALARM ACTIVATE switch, and finally the ALARM ACTIVATE switch again.<br />

3. Release the TONE SILENCE switch.<br />

Note: If both primary and secondary power sources are removed from the system, this setting will be lost. When<br />

power is restored, supervisory will default to latching operation.<br />

Standby Condition<br />

Green LED (AC power on) will be illuminated. All other LEDs (trouble and alarm) are off.<br />

System Trouble Condition<br />

Interruption of any of the electrically supervised circuits will illuminate the System Trouble LED. The<br />

Trouble Relay Contacts will transfer. The piezo (local buzzer) will sound one second on, one second off,<br />

and repeating until silenced. Silence the piezo by pressing the TONE SILENCE switch. The panel will<br />

remain in the trouble state until the trouble condition has been cleared and the panel reset.<br />

Alarm Condition<br />

Upon activation of an initiating device, a red alarm LED will illuminate for that zone. In addition, the Alarm<br />

Relay will activate, the piezo will sound, and Notification Appliance Circuit(s) will activate. (See “Output<br />

Circuits” on page 22 for details).<br />