2. Installation Optional Modules<br />

Setup and Configuration<br />

Transmitter Module - 4XTMF<br />

Connect a Remote Alarm circuit, Remote Trouble circuit or a Municipal Box to the Transmitter Module<br />

as shown below. Polarities shown in activated positions.<br />

Note: Dummy load terminals 6 and 7 (4.7K, 1/4 W resistor) if Municipal Box is not connected.<br />

Note: Remote Alarm, Remote Trouble and Municipal Box wiring can leave the building.<br />

Pushing the Disconnect Switch down will prevent unwanted activation of the Municipal Box during testing<br />

of the control panel. The Disconnect LED will remain illuminated while the Municipal Box is<br />

disconnected. The System Trouble LED will indicate disconnected and/or Open Circuit conditions on the<br />

Municipal Box.<br />

Cut the TBL Jumper to allow the alarm reverse polarity circuit to open on trouble, if no alarm exists.<br />

The wiring of this module must follow the requirements as specified under "Power-limited Wiring<br />

Requirements" on page 19.<br />

TBL Jumper<br />

TBL<br />

TB1<br />

+<br />

Remote Alarm (Power-limited)<br />

–<br />

+<br />

Remote Trouble (Power-limited)<br />

–<br />

No Connection<br />

+<br />

Municipal Box (Nonpower-limited)<br />

–<br />

Disconnect Switch<br />

J1<br />

Disconnect LED<br />

J2<br />

4XTMF.cdr<br />

Figure 15 4XTMF Configuration<br />

28 <strong>MS</strong>-<strong>4424</strong> <strong>Instruction</strong> <strong>Manual</strong> PN 15153:G1 10/22/02