2. Installation Optional Modules<br />
Setup and Configuration<br />
Transmitter Module - 4XTMF<br />
Connect a Remote Alarm circuit, Remote Trouble circuit or a Municipal Box to the Transmitter Module<br />
as shown below. Polarities shown in activated positions.<br />
Note: Dummy load terminals 6 and 7 (4.7K, 1/4 W resistor) if Municipal Box is not connected.<br />
Note: Remote Alarm, Remote Trouble and Municipal Box wiring can leave the building.<br />
Pushing the Disconnect Switch down will prevent unwanted activation of the Municipal Box during testing<br />
of the control panel. The Disconnect LED will remain illuminated while the Municipal Box is<br />
disconnected. The System Trouble LED will indicate disconnected and/or Open Circuit conditions on the<br />
Municipal Box.<br />
Cut the TBL Jumper to allow the alarm reverse polarity circuit to open on trouble, if no alarm exists.<br />
The wiring of this module must follow the requirements as specified under "Power-limited Wiring<br />
Requirements" on page 19.<br />
TBL Jumper<br />
TBL<br />
TB1<br />
+<br />
Remote Alarm (Power-limited)<br />
–<br />
+<br />
Remote Trouble (Power-limited)<br />
–<br />
No Connection<br />
+<br />
Municipal Box (Nonpower-limited)<br />
–<br />
Disconnect Switch<br />
J1<br />
Disconnect LED<br />
J2<br />
4XTMF.cdr<br />
Figure 15 4XTMF Configuration<br />
28 <strong>MS</strong>-<strong>4424</strong> <strong>Instruction</strong> <strong>Manual</strong> PN 15153:G1 10/22/02