Appendix B: NFPA Standard-Specific Requirements<br />
Digital Alarm Communicator/Transmitter - Noti-<strong>Fire</strong> 911AC<br />
Digital Alarm Communicator/Transmitter - Noti-<strong>Fire</strong> 911AC<br />
Note: This application is not FM approved<br />
Using the Noti-<strong>Fire</strong> 911AC DACT for connection to a Central Station Receiver or Protected Premises<br />
Receiving Unit.<br />
• AC Wiring for DACT/FACP must be connected to the same circuit.<br />
• If the unit is not mounted in the control panel’s backbox all connections must be in conduit, less<br />
than 20 feet (6.1 meters) in length in the same room.<br />
• For additional information refer to the Noti-<strong>Fire</strong> 911AC <strong>Instruction</strong> manual.<br />
See Below for Terminal<br />
Connections<br />
To Central<br />
Station<br />
To AC Power<br />
+<br />
–<br />
PS 1270<br />
12Volt<br />
7AH Battery<br />
<strong>MS</strong>-<strong>4424</strong> Control Panel<br />
IN #1<br />
IN #2<br />
IN #3<br />
IN #4<br />
B+ A+ A– B– B+ A+ A– B– B+ A+ A– B– B+ A+ A– B–<br />
TB3<br />
TB4<br />
JP1<br />
4XZMF Zone<br />
Relay Module<br />
TB1<br />
GEN<br />
ALM1<br />
GEN<br />
ALM2<br />
SUPV 1<br />
SUPR 2<br />
J2<br />
STD DACT<br />
LATCH<br />
DISABLE<br />
OPT1<br />
Jumper<br />
Place jumper over pins as shown when employing<br />
a DACT. This directs the control panel to transmit<br />
all trouble conditions except AC LOSS.<br />
TB3<br />
Figure 24 DACT Connections<br />
To Common<br />
Terminal of Relay<br />
<strong>MS</strong>44-911ac.cdr<br />