2. Installation Optional Modules<br />
LED Interface Module - 4XLMF<br />
Connect the terminals on TB1 of the LED Interface Module to the corresponding terminals of the RZA-<br />
4XF Remote Annunciator.<br />
Make wiring connections with system power off.<br />
Maximum wire impedance is 50 ohm per wiring connection.<br />
The wiring of this module must follow the requirements as specified under "Power-limited Wiring<br />
Requirements" on page 19.<br />
TB1<br />
+24V<br />
Out #1<br />
Out #2<br />
Out #3<br />
Out #4<br />
Sysyem Trouble<br />
Sound<br />
Resound<br />
J2<br />
Connect to corresponding<br />
terminals of the RZA-4XF<br />
Remote Annunciator.<br />
SYSTEM TROUBLE<br />
RE-SOUND<br />
TONE<br />
SILENCE<br />
FIRE ALARM ANNUNCIATOR<br />
Front View<br />
Side View<br />
Single-gang<br />
Box<br />
<strong>MS</strong>44--4xlmfconn.cdr<br />
Figure 18 Connection of 4XLMF to RZA-4XF<br />
30 <strong>MS</strong>-<strong>4424</strong> <strong>Instruction</strong> <strong>Manual</strong> PN 15153:G1 10/22/02