43<br />
Checking for Other Electrical Problems in Single-phase Motors<br />
This section provides procedures for checking the components such as the thermal protector,<br />
relay and capacitor in a single-phase compressor. Table 4-3 (below) can be used<br />
to locate the appropriate procedure for the compressor you are servicing. Examine the<br />
compressor and determine presence and/or the type of:<br />
• Thermal protector (internal or external)<br />
• Relay (current, potential or PTC)<br />
• Capacitor(s) (start or run)<br />
With that information, use Table 4-3 to determine the location of the procedure for the<br />
compressor you are servicing.<br />
For more information on:<br />
• <strong>Compressor</strong> motor types, see “Single-phase <strong>Compressor</strong> Motor Types” on pages 16-<br />
17.<br />
• Thermal protectors, see “<strong>Hermetic</strong> <strong>Compressor</strong> Thermal Protectors” on page 19.<br />
• Starting relays, see “<strong>Compressor</strong> Motor Starting Relays” on pages 21-24.<br />
• Capacitors, see “Selecting Capacitors” on pages 24-26.<br />
<strong>Compressor</strong> Motor<br />
Type<br />
Table 4-3: Locating Service Procedures by Component Types<br />
If your compressor has:<br />
Thermal Protector<br />
Relay Type<br />
Capacitor Type<br />
Type<br />
Internal External Current Potential PTC Run Start<br />
Go To:<br />
Page<br />
Resistance Start Induction<br />
Run (RSIR)<br />
(Split-Phase)<br />
Capacitor Start Induction<br />
Run (CSIR)<br />
Capacitor Start and<br />
Run (CSR)<br />
√ √ 44<br />
√ WIRED 46<br />
√ MODULE 48<br />
√ √ √ 50<br />
√ √ √ 53<br />
√ √ √ √ 56<br />
√ √ √ √ 59<br />
√ √ 62<br />
Permanent Split<br />
Capacitor (PSC)<br />
√ √ 64<br />
√ WIRED √ 66<br />
√ MODULE √ 68