28.01.2015 Views

Hermetic Compressor - Tecumseh

Hermetic Compressor - Tecumseh

Hermetic Compressor - Tecumseh

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

63<br />

Step 1: Before Continuing with Troubleshooting<br />

WARNING! All electric power should be disconnected and you should have already made sure<br />

that the compressor does not have a ground fault (see “Checking for a Ground Fault” on pages<br />

40-41). You should have also checked the windings for continuity and proper resistance (see<br />

“Checking for Continuity and Proper Resistance” on page 42), made sure the system is getting<br />

proper voltage, and that the control, thermostat, and contactor are working properly.<br />

Step 2: Check Wiring<br />

Confirm that there is continuity between C and the protector common lead wire.<br />

Step 3: Check External Thermal Protector<br />

Check for continuity across the thermal protector (line 1 and compressor terminal connection).<br />

If there is no continuity then the thermal protector may be tripped. Wait for the protector to cool<br />

off and close. This may take more than an hour. Check continuity gain. If there is no continuity,<br />

replace the protector.<br />

Step 4: Check Run Capacitor<br />

CAUTION: using a 20,000 ohm resistor, discharge the capacitor before removing it from the<br />

system to avoid damage to measuring devices and risk of electric shock. Disconnect the run<br />

capacitor from the system. Use a capacitance meter to check capacitor. Capacitance should<br />

be 10% of the marked capacitor value.<br />

As an alternative, check the run capacitor by measuring continuity across the capacitor terminals:<br />

• Rx1 scale: If there is continuity, then the run capacitor is shorted and needs to be replaced.<br />

• Rx100,000 scale: If there is no needle deflection on an analog meter or if a digital meter<br />

indicates infinite resistance, then the run capacitor is open and needs to be replaced.<br />

Possible reasons that a run capacitor is not working properly include:<br />

• Use of incorrect run capacitor. Replace with proper run capacitor.<br />

• Line voltage is too high (greater than 100% of rated voltage).<br />

Step 5: Reconnect Run Capacitor<br />

Reconnect the run capacitor into circuit at terminals S and R. (Marked terminal should go to R.)<br />

Step 6: Add Start Assist Kit<br />

If the compressor checks out satisfactorily on all the above PSC tests but still doesn’t operate,<br />

add proper start assist kit to provide additional starting torque. See Figure 4-11 for proper wiring.<br />

Step 7: Continue Troubleshooting<br />

If all above tests prove satisfactory and unit still fails to operate properly, check for adequate<br />

compressor pumping as outlined in the procedure on page 70.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!