28.01.2015 Views

Hermetic Compressor - Tecumseh

Hermetic Compressor - Tecumseh

Hermetic Compressor - Tecumseh

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

65<br />

Step 1: Before Continuing with Troubleshooting<br />

WARNING! All electric power should be disconnected and you should have already made<br />

sure that the compressor does not have a ground fault (see “Checking for a Ground Fault”<br />

on pages 40-41). You should have also checked the windings for continuity and proper<br />

resistance (see “Checking for Continuity and Proper Resistance” on page 42, made sure<br />

the system is getting proper voltage, and that the control, thermostat, and contactor are<br />

working properly.<br />

NOTE: the compressor housing MUST be at 130°F or less for the following checks. This<br />

temperature can be read by Tempstik or is that temperature which will allow the hand to<br />

remain in contact with the compressor housing without discomfort.<br />

Step 2: Check Internal Thermal Protector<br />

If there is continuity between all terminals the thermal protector should be good. If R to S<br />

has continuity and R to C and S to C do not, the thermal protector may be tripped. Wait<br />

for the protector to cool off and close. This may take more than an hour. Check continuity<br />

gain. If there is no continuity, replace the compressor.<br />

Step 3: Check Run Capacitor<br />

CAUTION: using a 20,000 ohm resistor, discharge the capacitor before removing it from<br />

the system to avoid damage to measuring devices and risk of electric shock. Disconnect<br />

the run capacitor from the system. Use a capacitance meter to check capacitor. Capacitance<br />

should be 10% of the marked capacitor value.<br />

As an alternative, check the run capacitor by measuring continuity across the capacitor<br />

terminals:<br />

• Rx1 scale: If there is continuity, then the run capacitor is shorted and needs to be<br />

replaced.<br />

• Rx100,000 scale: If there is no needle deflection on an analog meter or if a digital meter<br />

indicates infinite resistance, then the run capacitor is open and needs to be replaced.<br />

Possible reasons that a run capacitor is not working properly include:<br />

• Use of incorrect run capacitor. Replace with proper run capacitor.<br />

• Line voltage is too high (greater than 100% of rated voltage).<br />

Step 4: Reconnect Run Capacitor<br />

Reconnect the run capacitor into circuit at terminals S and R. (Marked terminal should go<br />

to R.)<br />

Step 5: Continue Troubleshooting<br />

If all above tests prove satisfactory and unit still fails to operate properly, check for adequate<br />

compressor pumping as outlined in the procedure on page 70.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!