RISK OF DAMAGE TO DC LOAD EQUIPMENT<br />

Equalization voltage may be as high as 15.8 volts DC. Disconnect<br />

sensitive loads from the battery before equalizing.<br />

Failure to follow these instructions can damage the unit and/or<br />

damage other equipment.<br />

Follow the battery manufacturer’s recommendations for equalizing your<br />

batteries. As a guide, a heavily used flooded battery may need to be<br />

equalized once a month, and a battery in light service may only need to be<br />

equalized every two to four months.<br />

Measure the specific gravity (S.G.) of each cell using a hydrometer. For<br />

fully charged lead-acid batteries, the reading should be approximately<br />

1.265. Low specific gravity after charging or a 0.25 difference from cell to<br />

cell indicates the need for equalization.<br />

Equalizing Batteries<br />

IMPORTANT: Equalization will be carried out after an absorption charge.<br />

Equalization only runs for 60 minutes and may need to be restarted if the<br />

specific gravity is still uneven.<br />

Operating The <strong>Freedom</strong> <strong>SW</strong> <strong>3000</strong><br />

To equalize your batteries:<br />

1. Turn off or disconnect all loads on the battery.<br />

The voltage applied to the battery during equalization may damage<br />

your electronic equipment. As well, equalization won’t proceed<br />

correctly if loads are drawing current from the battery.<br />

2. Check electrolyte level.<br />

Fill with distilled water if the electrolyte level is low.<br />

3. To request the equalization charge, ensure the <strong>Charger</strong> is enabled.<br />

4. On the SCP, select Equalize on the <strong>Freedom</strong> <strong>SW</strong> <strong>3000</strong> home menu.<br />

For detailed information on configuring this setting, refer to<br />

“Equalize” on page 34.<br />

5. When equalization is finished, check the battery electrolyte level. Top<br />

up as necessary with distilled water only and recheck the specific<br />

gravity as specified by the battery manufacturer.<br />

Terminating the Equalization Process<br />

The equalization process can be terminated in three ways:<br />

• user cancellation from the SCP, as shown in Figure 24 on page 36,<br />

• inverter/charger cancellation if AC is removed or the charger is<br />

disabled, or<br />

• a successful completion of the equalization process.<br />

975-0545-01-01 19