<strong>Model</strong> <strong>MR</strong> Operation and <strong>Installation</strong> <strong>Manual</strong><br />
Setup<br />
Press any button<br />
to Enter Menu<br />
‘Enter’ or ‘Carriage Return’<br />
Down arrow button<br />
Up arrow button<br />
To exit Calibration Mode<br />
at any time, press all three<br />
buttons simultaneously:<br />
+ +<br />
Accept new value?<br />
If No: +<br />
If Yes:<br />
Calibrate Level 1?<br />
= Calibrate Span<br />
= Calibrate Zero<br />
Reads current float<br />
position, Move float<br />
to desired position<br />
+ hold for 1 second<br />
Setup<br />
Calibrate Level 2?<br />
= Calibrate Span<br />
= Calibrate Zero<br />
Reads current float<br />
position, Move float<br />
to desired position + hold for 1 second<br />
Increases Value<br />
Adjust<br />
LCD Contrast?<br />
Shows current<br />
LCD contrast value<br />
Accept new value?<br />
If No: +<br />
If Yes:<br />
+ hold for 1 second<br />
Decreases Value<br />
Perform<br />
LCD Test?<br />
Tests all segments<br />
of LCD<br />
(lasts 10 seconds)<br />
Figure 15. <strong>Manual</strong> calibration matrix<br />
Level Plus ® Liquid-Level <strong>Sensors</strong> - M-Series <strong>Model</strong> <strong>MR</strong> Analog Transmitter<br />
Operation and <strong>Installation</strong> <strong>Manual</strong>, Document Number 550720 Revision G, 09/11 EN 20<br />