OPERATOR FUNCTIONS (RUN MODE)Oxygen 5.1% AFire 85% SP 5.2Power Alarm Setup NeutralDisplayAlarmTrimSetupNeutralTrimFunctionOptionRunPurgeTrimTrimEnableAuto/ManFunctionOptionEnterAutocal4.1 DISPLAY BUTTONThe upper line on the display will always read % oxygen. The following are available for display on the lower line.1. Run hours since last service2. Date of last service3. Boiler firing rate / oxygen set point4. Trim actuator position5. Probe EMF (millivolts)6. Probe temperature7. Auxiliary temperature8. Probe impedance, A measure of integrity of the sensor's electrode, the part of the probe that normally wears outfirst.9. Ambient temperature10. Boiler efficiency %11. Oxygen deficiency %12. Combustibles %13. Carbon dioxide %, dry. Calculated from the oxygen reading. Assumes complete combustion.Any number of these variables can be displayed sequentially by pressing the ‘DISPLAY’ button. Items can be selectedfor display or deleted in Set-up step 29 on the keyboard. In addition to the above lower line displays, the analyser willautomatically display:“Probe Temp Low”, when the oxygen probe is below 650°C (1200°F)“Gas ON” for Calibration check Gas 1“Purging Probe”“Probe Thermocouple Wrong Polarity”“Aux Thermocouple Wrong Polarity”August 200936 <strong>1633</strong> <strong>Combustion</strong> <strong>Controller</strong>