23.11.2012 Views

General Catalogue 2007 - Ibemo Kazakhstan Ltd

General Catalogue 2007 - Ibemo Kazakhstan Ltd

General Catalogue 2007 - Ibemo Kazakhstan Ltd

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Fig 14<br />

Time in Seconds<br />

10000<br />

6000<br />

4000<br />

3600<br />

2000<br />

1000<br />

600<br />

400<br />

200<br />

100<br />

60<br />

40<br />

20<br />

10<br />

6<br />

4<br />

2<br />

1<br />

0,6<br />

0,4<br />

0,2<br />

0,1<br />

0,04<br />

0,02<br />

0,01<br />

0,004<br />

1 1,5 2 3 4 6 8 10 15 20 30 40<br />

1,13<br />

1,45<br />

Multiples of In<br />

C<br />

S<br />

M<br />

Feeder<br />

circuit<br />

breaker<br />

Remote<br />

starter<br />

Motor<br />

Direct start<br />

Full load Full load Starting Starting<br />

speed current current torque<br />

kW hp rev/min A x FLC x FLC<br />

2800 3.2 6.75 3<br />

1400 3.5 5.5 2.5<br />

1.5 2 900 3.8 4.5 2.2<br />

700 4.3 4.0 2.0<br />

Table 27<br />

Fig 15<br />

Hager <strong>Catalogue</strong> <strong>2007</strong> • Technical<br />

MCCB Motor Power Circuit Protection<br />

Motor Power Circuit Protection<br />

The selection of the circuit protective device for motor power supply<br />

circuits depends in the first instance on the relative physical position<br />

of the various circuit elements. The feeder circuit breaker in the<br />

switchboard, panelboard or distribution board, the starter with its<br />

contactor and thermal overload relay, with perhaps its own isolator or<br />

short-circuit protective device (SCPD) and of course the motor.<br />

The feeder circuit breaker, which can be a perfectly standard thermal<br />

magnetic breaker, must protect the cable feeding the starter so the<br />

normal selection criteria apply. In addition, however, it must be able<br />

to withstand the inrush and starting currents of the motor without<br />

nuisance tripping. The inrush current, which should not be confused<br />

with the starting current, appears at the instant of switch on and<br />

could be as great as 10 times the full load current (FLC) of the motor,<br />

but with a relatively short pulse time of 20 to 30 milliseconds.<br />

The starting current of a direct on line (DOL) start squirrel cage<br />

motor does vary with the designed speed of the motor - the higher<br />

the speed the higher the starting torque and the starting current as<br />

a ratio of the FLC. However the FLC is inversely proportional to the<br />

design speed of the motor. Table 27 shows typical performance data<br />

for average 1.5kw/2hp three phase squirrel cage motors.<br />

The run-up time can vary between one and fifteen seconds<br />

depending on the surge of the motor and the type of load the motor<br />

is driving.<br />

Clearly then, to accurately select the correct circuit breaker for a<br />

motor power supply circuit it is essential to know the correct FLC, the<br />

starting current and the run-up time. This information is then plotted<br />

against the time/current characteristic curve of the type of circuit<br />

breaker (or fuse) selected.<br />

Example<br />

Select an appropriate feeder circuit breaker to supply a 1.5kw 3<br />

phase motor DOL start. FLC 3.5A, starting current 5.5 x FLC, run-up<br />

time 6 secs. The circuit breaker must be suitable for fitting into a 3<br />

phase MCB Distribution Board.<br />

Starting current: 3.5 x 5.5 = 19.25A for 6 secs<br />

Inrush current : 3.5 x 10 = 35A<br />

Comparing the data against the time/current characteristics of a type<br />

C MCB, Fig 15, we see that at 6 secs the breaker will carry 2 x In<br />

without tripping. Therefore a 10A MCB would carry 20A for 6 secs.<br />

The minimum instantaneous trip for this type C MCB would be 50A.<br />

Therefore the closest protection for this motor feeder circuit would<br />

be a 3 Pole 10A type C MCB. A 10A type D could be used providing<br />

the 100A maximum instantaneous trip was not a problem. The inrush<br />

current would preclude the use of a 10A type B because the<br />

minimum instantaneous trip is only 30A. In this case use the next<br />

size up, i.e. 16A.<br />

ibemo <strong>Kazakhstan</strong> - 090301 Republic of <strong>Kazakhstan</strong>, West <strong>Kazakhstan</strong> Oblast, Aksai, Pramzone, BKKS office complex<br />

Phone: +7 71133 93077 ; Fax: +7 71133 93074 ; E-Mail: info@ibemo-kz.com<br />

3.43<br />

Protection<br />

Devices

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!