Instructions for use<br />

Changing Pre-set parameters<br />

1. Set dill switches to ON or OFF according to desired settings.<br />

2. Hold the programmer vertically beneath the occupancy<br />

sensor and press button A. The detector turns its load OFF<br />

to indicate the beginning of a programming event and turns<br />

back on almost immediately if the operation is a success. If<br />

the detector output does not turn back on, repeat the<br />

operation.<br />

Parameter options for OS3/D, OS3/DS, OS4/D, OS4/DS, OS3/DSW and OS4/DSW<br />

10.10<br />

Options at end off delay<br />

{<br />

Fade to<br />

off = Yes 5 min 10 min 20 min<br />

Hager <strong>Catalogue</strong> <strong>2007</strong> • Technical<br />

OSDP Digital Programmer<br />

Setting the regulating light level<br />

1. Point this unit at the occupancy sensor and adjust the light<br />

output using the UP/DOWN buttons until the desired light<br />

level is achieved locally.<br />

Note: that it may not be possible to do this in the presence of<br />

strong natural light.<br />

2. Press STORE, two seconds later the load (regulating ballasts)<br />

blinks to indicate a successful store operation. The occupancy<br />

sensor will now regulate the light output in order to maintain the<br />

level of illuminance at this new set point.<br />

All of these parameters will be preserved in the event of power<br />

loss and can be re-programmed any number of times.<br />

1 2 3 4 5 6 7 8 9 10 11 12<br />

Fade to<br />

off = No<br />

{<br />

Off delay add together to<br />

give required time<br />

(All off = 10 sec walk test)<br />

Off Off Off Lights turn off<br />

On Off Off Lights stay at minimum output until next occupancy<br />

Off On On Lights regulate below 25% for 3 hours then turn off<br />

Off On Off Lights regulate below 25% until next occupancy<br />

On Off On Lights stay at minimum output for 3 hours then turn off<br />

Optimum settings to perform 10 second walk test<br />

Switches Status<br />

1-9 Off<br />

10-12 On<br />

Minimum<br />

on-time<br />

= 20 min<br />

Minimum<br />

on-time<br />

= off delay<br />

Bright-out<br />

= Yes<br />

Bright-out<br />

= No<br />

Occupancy<br />

sensor<br />

automatic<br />

operation<br />

Occupancy<br />

sensor semi<br />

-automatic<br />

operation<br />

Start<br />

Full<br />

Start<br />

Low<br />

Power Up<br />

On<br />

Power Up<br />

Off<br />

ibemo <strong>Kazakhstan</strong> - 090301 Republic of <strong>Kazakhstan</strong>, West <strong>Kazakhstan</strong> Oblast, Aksai, Pramzone, BKKS office complex<br />

Phone: +7 71133 93077 ; Fax: +7 71133 93074 ; E-Mail: info@ibemo-kz.com<br />

On<br />

Off