Motor DOL starting Assisted start<br />

rating conditions conditions<br />

Up to 0.75kW 5 x FLC for 6 secs 2.5 x FLC for 15 secs<br />

1.1 to 7.5 kW 6 x FLC for 10 secs 2.5 x FLC for 15 secs<br />

11 to 75kW 7 x FLC for 10 secs 2.5 x FLC for 15 secs<br />

90 to 160kW<br />

Table 28<br />

6 x FLC for 15 secs 2.5 x FLC for 20 secs<br />

1 Phase 230V DOL Starting<br />

Recommended circuit breaker<br />

FLC (A) HN<br />

kW hp A NBN NCN NDN Fuse(A)<br />

0.18 0.25 2.8 16 10 10 10<br />

0.25 0.33 3.2 16 10 10 16<br />

0.37 0.5 3.5 16 10 10 16<br />

0.55 0.75 4.8 20 16 16 16<br />

0.75 1.0 6.2 25 20 20 20<br />

1.1 1.5 8.7 40 25 25 25<br />

1.5 2.0 11.8 50 32 32 32<br />

2.2 3.0 17.5 - 50 50 40<br />

3.0 4.0 20 - 63 63 50<br />

3.75 5.0 24 - - - 63<br />

5.5 7.5 36 - - - 80<br />

7.5<br />

Table 29<br />

10 47 - - - 100<br />

3 Phase 400V Assisted Starting Star-Delta<br />

Recommended circuit breaker<br />

FLC (A) (A) HRC<br />

kW hp A NCN NDN fuse (A)<br />

3 4 6.3 16 10 16<br />

4 5.5 8.2 20 10 16<br />

5.5 7.5 11.2 32 16 20<br />

7.5 10 14.4 40 25 25<br />

11 15 21 50 32 32<br />

15 20 27 40 35<br />

18.5 25 32 50 40<br />

22 30 38 63 50<br />

30 40 51 63<br />

37 50 63 80<br />

45 60 76 80<br />

55 75 91 100<br />

75 100 124 160<br />

90 125 154 200<br />

110 150 183 200<br />

132 175 219 250<br />

150 200 240 315<br />

160<br />

Table 30<br />

220 257 315<br />

3.44<br />

Hager <strong>Catalogue</strong> <strong>2007</strong> • Technical<br />

Device Selection For Motor Applications<br />

Tables 28,29,30 and 31 give general recommendations for the<br />

selection of circuit breakers and HRC fuses for the protection of<br />

motor power circuits and are based on the assumptions shown in<br />

Table 28 for a cage motor running at approximately 1400 Rev/Min.<br />

Assisted Start<br />

The selection of a feeder circuit breaker for a motor with an assisted<br />

start facility is much the same as for DOL start. The full load running<br />

current is the same for both, but the starting current for the assisted<br />

start can be less than half, with a subsequent reduction in starting<br />

torque. Typical starting current for star-delta start would be 2 to<br />

21/2 times FLC, with a run-up time of 15 to 20 seconds depending<br />

on the size of the motor and the load driven by the motor. However<br />

the transient during changeover still has to be taken into account so<br />

selection is often dictated by the instantaneous trip setting of the<br />

circuit breaker.<br />

3 Phase 400V DOL Starting<br />

Recommended circuit breaker<br />

FLC (A) (A) (A) HRC<br />

kW hp A NBN NCN NDN fuse (A)<br />

0.18 0.25 0.87 2 4<br />

0.25 0.33 1.17 3 4<br />

0.37 0.5 1.2 3 4<br />

0.55 0.75 1.8 4 6<br />

0.75 1.0 2.0 10 6 6 6<br />

1.1 1.5 2.6 16 10 6 10<br />

1.5 2.0 3.5 16 10 10 16<br />

2.2 3.0 4.4 20 16 16 16<br />

3.0 4.0 6.3 25 20 20 20<br />

4.0 5.5 8.2 32 25 25 25<br />

5.5 7.5 11.2 50 40 40 32<br />

7.5 10 14.4 63 50 50 40<br />

11 15 21 63<br />

15 20 27 80<br />

18.5 25 32 80<br />

22 30 38 80<br />

30 40 51 100<br />

37 50 63 125<br />

45 60 76 125<br />

55 75 91 160<br />

75 100 124 200<br />

90 125 154 250<br />

110 150 183 315<br />

132 175 219 355<br />

150 200 240 355<br />

160<br />

Table 31<br />

220 257 355<br />