HQD6L3– Multi-DeckApplication:35CASE DATA 04 06 08 12Anti-Sweat Amps NA NA NA NAFan Amps PSC 0.37 0.52 0.74 1.11Light Amps (Two rows canopy) 0.50 0.80 1.00 1.50Defrost Load Amps None None None None# Defrosts Required 3 3 3 3BTU Req. @ +30 °F(unlighted shelves) 5400 8100 10800 16200BTU Req. @ +27°F(lighted shelves) 5820 8750 11640 17460NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.electrical data based on 115V and unlighted shelves. Add 0.063 amps per foot fornose light and .25 amps per shelf for lighted shelves.Defrost Per Day Fail Safe TerminationOff Cycle 3 40 min 48°Hot gas 3 20 Min 48°AllDischarge Air VelocityDischarge Air Temp250 FPM32°F (Lit) +34°F (unlit)Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 05