<strong>Planning</strong>ManualSept 20, 2006Part No. 31E11021Date: 9/20/065201 Transport Blvd. Columbus, GA 31907solutions@kysorwarren.comwww.kysorwarren.com800-866-5596


Table of Contents3PRODUCT Page #Single Deck 4Produce 5-6Deli/Bakery/Cheese 7-8Meat/Fish 9-12Frozen 13-19Multi-Deck 20Produce 21-24Dairy 25-32Deli/Bakery/Cheese 33-35Meat/Fish 36-42Frozen 43Specialty 44Bakery/Cheese 45-47Pizza/Cheese/Deli 48-55Deli/Meat/Produce 56-62PRODUCT Page #Glass Door 63Standard Line 64-69Taller Line 70-71Narrow Line 72-74Back-to-Back 75-77Island 78Produce 79-81Deli/Bakery/Cheese 82-93Meat/Fish 94Frozen 95-106Services 107Meat / Fish 108-117Deli 118-126Hot 127-130Other 131-136


Single Deck Cases4


ZV3– Single DeckApplication:5CASE DATA 04 06 08 12Anti-Sweat Amps N/A N/A N/A N/AFan Amps .53 .53 .53 1.06Light Amps N/A N/A N/A N/ADefrost Load Amps None None None None# Defrosts Required 4 4 4 4Evaporator Temperature °F +20° +20° +20° +20°BTU Requirements 1700 2550 3400 5100NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationOff Cycle 4 40 min 55°Discharge Air Velocity176 - 191 FPMDischarge Air Temp 34 - 40°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


ZHV3– Single DeckApplication:6CASE DATA 08 12Anti-Sweat Amps N/A N/AFan Amps .53 1.06Light Amps N/A N/ADefrost Load Amps None None# Defrosts Required 4 4Evaporator Temperature °F +20° +20°BTU Requirements 4680 7020NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationOff Cycle 4 40 min 55°Discharge Air Velocity150 - 175 FPMDischarge Air Temp 34 - 40°Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


VPA-950-12 Single DeckApplication:7CASE DATA 4’ 8’Anti-Sweat Amps NA NAFan Amps 0.70 1.05Light Amps NA NADefrost Load Amps (If electric) NA NA# Defrosts Required 4 4Evaporator Temperature °F 20°F 20°FBTU Requirements 2600 5200NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationOff Cycle 4 45 min 55°Super Heat 6-8Discharge Air Temp 26-28Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 06


VPA-1250-12 Single DeckApplication:8CASE DATA 4’ 8’Anti-Sweat Amps NA NAFan Amps 0.70 1.05Light Amps NA NADefrost Load Amps (If electric) NA NA# Defrosts Required 4 4Evaporator Temperature °F 20°F 20°FBTU Requirements 2600 5200NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationOff Cycle 4 45 min 55°Super Heat 6-8Discharge Air Temp 26-28Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 06


QM1A3– Single DeckApplication:9CASE DATA 04A 06A 08A 12AAnti-Sweat Amps 0.06 0.08 0.12 0.18Fan Amps (SP) 0.34 0.68 0.68 1.02Light Amps N/A N/A N/A N/ADefrost Load Amps (If elec-230V) 3.30 5.61 7.93 11.54# Defrosts Required 4 4 4 4Evaporator Temperature °F +24° +24° +24° +24°BTU Requirements 2000 3000 4000 6000NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationOff Cycle 4 35 min 48°Hot gas 4 18 min 48°Electric 4 35 min 48°Discharge Air Velocity150 FPMDischarge Air Temp 27°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


QM1AG3– Single DeckApplication:10CASE DATA 04A 06A 08A 12AAnti-Sweat Amps 0.06 0.08 0.12 0.18Fan Amps 0.34 0.68 0.68 1.02Light Amps N/A N/A N/A N/ADefrost Load Amps (If electric 230V) 3.30 5.61 7.93 11.54# Defrosts Required 4 4 4 4Evaporator Temperature °F +24° +24° +24° +24°BTU Requirements 1920 2880 3840 5760NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationOff Cycle 4 35 min 48°Hot gas 4 18 min 48°Electric 4 35 min 48°Discharge Air Velocity150 FPMDischarge Air Temp 27°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 2006


M1ALG3– Single DeckApplication:11CASE DATA 04 06 08 12Anti-Sweat Amps .35 .47 .59 .82Fan Amps .37 .37 .37 .74Light Amps N/A N/A N/A N/ADefrost Load Amps (If elec-230V) 3.30 5.61 7.93 11.54# Defrosts Required 3 3 3 3Evaporator Temperature °F +15° +15° +15° +15°BTU Requirements 1980 2970 3960 5940NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationOff Cycle 3 40 min 55°Hot gas 3 18 min 55°Electric 3 30 min 55°Discharge Air Velocity225 - 250 FPMDischarge Air Temp 22 - 26°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


M1AL3– Single DeckApplication:12CASE DATA 04 06 08 12Anti-Sweat Amps .11 .16 .22 .33Fan Amps .37 .37 .37 .74Light Amps N/A N/A N/A N/ADefrost Load Amps (If elec-230V) 3.30 5.61 7.93 11.54# Defrosts Required 3 3 3 3Evaporator Temperature °F +15° +15° +15° +15°BTU Requirements 2080 3200 4160 6240NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationOff Cycle 3 40 min 55°Hot gas 3 18 min 55°Electric 3 30 min 55°Discharge Air Velocity225 - 250 FPMDischarge Air Temp 22 - 26°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


LM13– Single Deck FrozenApplication:13CASE DATA 04 06 08 12Anti-Sweat Amps N/A N/A 1.10 1.70Fan Amps N/A N/A .80 1.70Light Amps N/A N/A N/A N/ADefrost Load Amps (If elec-230V) N/A N/A 9.37 14.06# Defrosts Required N/A N/A 1 1Evaporator Temperature °F N/A N/A -25° -25°BTU Requirements N/A N/A 3960 5940NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 1 30 min 55°Discharge Air VelocityDischarge Air Temp150 FPM-15°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has caselengths that are NSF approved.Issue: Sept - 06


LM1G3– Single Deck FrozenApplication:14CASE DATA 04 06 08 12Anti-Sweat Amps N/A 1.56 1.35 2.13Fan Amps N/A .53 .80 1.70Light Amps N/A N/A N/A N/ADefrost Load Amps (If elec-230V) N/A 5.61 9.37 14.06# Defrosts Required N/A 1 1 1Evaporator Temperature °F N/A -25° -25° -25°BTU Requirements N/A 2970 3960 5940NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 1 30 min 55°Discharge Air VelocityDischarge Air Temp150 FPM-15°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has caselengths that are NSF approved.Issue: Sept - 06


XL3– Single Deck FrozenApplication:15CASE DATA 06 08 12Anti-Sweat Amps 1.47 1.39 2.43Fan Amps (SP) .94 .94 .94Light Amps 0.47 0.70Drain Heater Amps. 0.39 0.39 0.83Defrost Load Amps (If elec-230V) 6.52 9.37 14.06# Defrosts Required 1 1 1BTU Requirements at a -20°F 2400 3200 4800BTU Requirements at a –30°F 2490 3320 4980NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 1 60 55°FDischarge Air VelocityDischarge Air Temp120-130 FPM-8°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


XLG3– Single Deck FrozenApplication:16CASE DATA 06 08 12Anti-Sweat Amps 1.37 1.38 2.25Fan Amps (SP) .94 .94 .94Fan Amps (PSC) 0.78 0.78 0.78Light Amps 0.47 0.70Drain Heater Amps. 0.39 0.39 0.83Defrost Load Amps (If elec-230V) 6.52 9.37 14.06# Defrosts Required 1 1 1BTU Requirements at -20°F 2550 3400 5100BTU Requirements at -30°F 2710 3520 5280NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 1 60 55°FDischarge Air VelocityDischarge Air Temp120-130 FPM-8°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has caselengths that are NSF approved.Issue: Sept - 06


XLGN1– Single Deck Narrow FrozenApplication:17CASE DATA 06 08 12Anti-Sweat Amps 1.37 1.38 2.25Fan Amps (SP) .94 .94 .94Light Amps 0.47 0.70Drain Heater Amps. 0.39 0.39 0.83Defrost Load Amps (If elec-230V) 6.52 9.37 14.06# Defrosts Required 1 1 1BTU Requirements at -20°F 2550 3400 5100BTU Requirements at -30°F 2710 3520 5280NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 1 60 55°FDischarge Air VelocityDischarge Air Temp120-130 FPM-8°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has caselengths that are NSF approved.Issue: Sept - 06


LG3– Single Deck FrozenApplication:18CASE DATA 06 08 12Anti-Sweat Amps N/A 1.34 2.02Fans Amps N/A .94 .94Light Amps N/A N/A N/ADrain Heater Amps 0.06 0.39 0.83Defrost Load Amps (If elec-230V) N/A 9.37 14.06# Defrosts Required N/A 1 1Evaporator Temperature °F N/A -20° -20°BTU Requirements N/A 3400 5100NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 1 60 55°FDischarge Air VelocityDischarge Air Temp120-130 FPM-8°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 06


LBHG3– Single Deck FrozenApplication:19CASE DATA 06 08 12Anti-Sweat Amps 1.37 1.34 2.02Fan Amps .79 .94 .94Light Amps N/A N/A N/ADrain Heater Amps. 0.13 0.39 0.83Defrost Load Amps (If elec-230V) 6.52 9.37 14.06# Defrosts Required 1 1 1Evaporator Temperature °F -20° -20° -20°BTU Requirements 2550 3400 5100NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 1 60 55°FDischarge Air VelocityDischarge Air Temp120-130 FPM-8°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has caselengths that are NSF approved.Issue: Sept - 06


Multi-Deck Cases20


QHZVP3– Multi-DeckApplication:21CASE DATA 04 06 08 12Anti-Sweat Amps N/A N/A N/A N/AFan Amps Std. 0.53 0.70 1.04 1.56Light Amps (double rows) 0.50 0.80 1.00 1.50Defrost Load Amps None None None None# Defrosts Required 3 3 3 3BTU Req. @ +26 °F (cut produce) 5080 7620 10160 15240BTU Req. @ +32 °F (bulk produce) 5040 7560 10080 15120NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lighted shelves, pleaseadd 98 BTU and .25 amps per shelf.Defrost Per Day Fail Safe TerminationOff Cycle 3 40 min 48°Hot Gas 3 20 min 48°Discharge Air Velocity275 FPMDischarge Air Temp 31 - 37 °FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


H3ZVP3– Multi-DeckApplication:22CASE DATA 06’ 08’ 12’Anti-Sweat Amps N/A N/A N/AFan Amps N/A .68 1.02Light Amps (two rows) N/A .90 1.54Defrost Load Amps N/A None None# Defrosts Required N/A 4 4Evaporator Temperature °F N/A +20° +20°BTU Requirements N/A 9120 13,680NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lightedshelves, please add 98 BTU and .25 amps per shelf.Defrost Per Day Fail Safe TerminationOff Cycle 4 40 min 55°Discharge Air Velocity 325 - 375 FPMDischarge Air Temp 34 - 40°Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


QD6L3– Multi-DeckApplication:23CASE DATA 04 06 08 12Anti-Sweat Amps NA NA NA NAFan Amps 0.52 0.70 1.04 1.56Light Amps (Two rows canopy) 0.46 0.92 0.92 1.48Defrost Load Amps None None None None# Defrosts Required 4 4 4 4Evaporator Temperature °F +23° +23° +23° +23°BTU Requirements 5540 8310 11080 16620NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lighted shelves, please add 98BTU and 0.25 amps per shelf. Add 0.063 amps per foot for nose light.Defrost Per Day Fail Safe TerminationOff Cycle 4 30 min 48°Hot gas 4 20 Min 48°Discharge Air VelocityDischarge Air Temp275 FPM31.5°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


QD6L3– Multi-DeckApplication with Gourmet Insert:24CASE DATA 04 06 08 12Anti-Sweat Amps NA NA NA NAFan Amps 0.52 0.70 1.04 1.56Light Amps (Two rows canopy) 0.46 0.92 0.92 1.48Defrost Load Amps None None None None# Defrosts Required 4 4 4 4Evaporator Temperature °F +23° +23° +23° +23°BTU Requirements 5540 8310 11080 16620NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lighted shelves, pleaseDefrost Per Day Fail Safe TerminationOff Cycle 4 30 min 48°Hot gas 4 20 min 48°Discharge Air VelocityDischarge Air Temp275 FPM31.5°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


QD63– Multi-DeckApplication:25CASE DATA 04 06 08 12Anti-Sweat Amps NA NA NA NAFan Amps 0.52 0.70 1.04 1.56Light Amps (Two rows canopy) 0.46 0.92 0.92 1.48Defrost Load Amps None None None None# Defrosts Required 4 4 4 4Evaporator Temperature °F +23° +23° +23° +23°BTU Requirements 5200 7800 10400 15600NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lighted shelves, pleaseadd 98 BTU and .25 amps per shelf. Add 0.063 amps per foot for nose light.Defrost Per Day Fail Safe TerminationOff Cycle 4 30 min 48°Hot gas 4 20 Min 48°Discharge Air VelocityDischarge Air Temp275 FPM31.5°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


D73– Multi-DeckApplication:26CASE DATA 06 08 12Anti-Sweat Amps N/A N/A N/AFan Amps 1.06 1.06 1.59Light Amps (Two rows canopy) 0.90 .92 1.48Defrost Load Amps None None None# Defrosts Required 4 4 4Evaporator Temperature °F +20° +20° +20°BTU Requirements 10320 13760 20640NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lightedshelves, please add 98 BTU and .25 amps per shelf. Add 0.063 ampsper foot for nose light.Defrost Per Day Fail Safe TerminationOff Cycle 4 40 min 55°Hot gas 4 20 min 55°Discharge Air Velocity275 - 375 FPMDischarge Air Temp 28 - 32°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


D73– 88” TallApplication:27CASE DATA 06 08 12Anti-Sweat Amps N/A N/A N/AFan Amps 1.06 1.06 1.59Light Amps (Two rows canopy) 0.90 .92 1.48Defrost Load Amps None None None# Defrosts Required 4 4 4Evaporator Temperature °F +20° +20° +20°BTU RequirementsNOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lightedshelves, please add 98 BTU and .25 amps per shelf. Add 0.063 ampsper foot for nose light.Defrost Per Day Fail Safe TerminationOff Cycle 4 40 min 55°Hot gas 4 20 min 55°Discharge Air Velocity275 - 375 FPMDischarge Air Temp 28 - 32°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 06


D7G1– Multi-DeckApplication:28CASE DATA 06 08 12Anti-Sweat Amps N/A N/A N/AFan Amps 1.06 1.06 1.59Light Amps (Two rows canopy) 0.90 .92 1.48Defrost Load Amps None None None# Defrosts Required 4 4 4Evaporator Temperature °F +20° +20° +20°BTU RequirementsNOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lightedshelves, please add 98 BTU and .25 amps per shelf. Add 0.063 ampsper foot for nose light.Defrost Per Day Fail Safe TerminationOff Cycle 4 40 min 55°Hot gas 4 20 min 55°Discharge Air Velocity275 - 375 FPMDischarge Air Temp 28 - 32°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 06


D6RL3– Multi-DeckApplication:29CASE DATA 04 06 08 12Anti-Sweat Amps NA NA NA NA# Of Fans/Amps* 1/1.06 2/1.59 2/2.12 3/3.18Light Amps (Two rows canopy) .46 .92 .92 1.48Defrost Load Amps None None None None# Defrosts Required 6 6 6 6Evaporator Temperature °F +20° +20° +20° +20°BTU Requirements 6000 9000 12000 18000NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lighted shelves,please add 98 BTU and .25 amps per shelf. Add 0.063 amps per foot forDefrost Per Day Fail Safe TerminationOff Cycle 6 40 min 55°Hot gas 6 20 min 55°Electric 6 30 min 55°Discharge Air Velocity400– 500 FPMDischarge Air Temp 26 - 30°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 2006


D6NL1– Multi-Deck NarrowApplication:30CASE DATA 04 06 08 12Anti-Sweat Amps NA NA NA NAFan Amps NA NA 1.06 1.59Light Amps (Two rows canopy) NA NA 0.92 1.48Defrost Load Amps NA NA None None# Defrosts Required NA NA 4 4Evaporator Temperature °F NA NA +20° +20°BTU Requirements NA NA 11600 17400NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lighted shelves, pleaseadd 98 BTU and .25 amps per shelf. Add 0.063 amps per foot for nose light.Defrost Per Day Fail Safe TerminationOff Cycle 4 30 min 55°Hot gas 4 20 min 55°Discharge Air VelocityDischarge Air Temp275 FPM31.5°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 06


D7N3– Multi-Deck NarrowApplication:31CASE DATA 04 06 08 12Anti-Sweat Amps NA NA NA NAFan Amps NA NA 1.06 1.59Light Amps (Two rows canopy) NA NA 0.92 1.48Defrost Load Amps (If elec-230V) NA NA 7.93 11.54# Defrosts Required NA NA 4 4Evaporator Temperature °F NA NA +20° +20°BTU Requirements NA NA 12530 18800NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lighted shelves, pleaseadd 98 BTU and .25 amps per shelf. Add 0.063 amps per foot for nose light.Defrost Per Day Fail Safe TerminationOff Cycle 4 30 min 55°Hot gas 4 20 min 55°Electric 6 30 min 55°Discharge Air Velocity FPMDischarge Air Temp °FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 06


D7NH3– Multi-Deck NarrowApplication:32CASE DATA 04 06 08 12Anti-Sweat Amps NA NA NA NAFan Amps NA NA 1.06 1.59Light Amps (Two rows canopy) NA NA 0.92 1.48Defrost Load Amps (If elec-230V) NA NA 7.93 11.54# Defrosts Required NA NA 4 4Evaporator Temperature °F NA NA +20° +20°BTU Requirements NA NA 13760 20640NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lighted shelves, pleaseadd 98 BTU and .25 amps per shelf. Add 0.063 amps per foot for nose light.Defrost Per Day Fail Safe TerminationOff Cycle 4 30 min 55°Hot gas 4 20 min 558°Electric 6 30 min 55°Discharge Air Velocity FPMDischarge Air Temp °FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 06


QD6H3 – Multi-DeckApplication:33CASE DATA 04 06 08 12Anti-Sweat Amps NA NA NA NAFan Amps 0.52 0.70 1.04 1.56Light Amps (Two rows canopy) 0.46 0.92 0.92 1.48Defrost Load Amps (If electric) None None None None# Defrosts Required 4 4 4 4BTU Requirements at +23° 4800 7200 9600 14400NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lighted shelves,please add 98 BTU and .25 amps per shelf. Add 0.063 amps per foot for nose light.Defrost Per Day Fail Safe TerminationOff Cycle 4 30 min 48°Hot gas 4 20 min 48°Discharge Air VelocityDischarge Air Temp275 FPM31.5°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 degF and 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


HQD63– Multi-DeckApplication:34CASE DATA 04 06 08 12Anti-Sweat Amps NA NA NA NAFan Amps PSC 0.37 0.52 0.74 1.11Light Amps (Two rows canopy) 0.50 0.80 1.00 1.50Defrost Load Amps None None None None# Defrosts Required 3 3 3 3BTU Req. @ +30°F (unlighted shelves) 5040 7560 10080 15120*BTU Req. @ +27°F (lighted shelves) 5420 8130 10840 16260NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. Add 0.063 amps per foot fornose light and .25 amps per shelf for lighted shelves.* At +27°F evap wire lighted shelves, add 19 Btu/Hr/Ft per rowDefrost Per Day Fail Safe TerminationOff Cycle 3 40 min 48°Hot gas 3 20 Min 48°Discharge Air VelocityDischarge Air Temp250 FPM32°F(Lit) +34°F(unlit)_Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


HQD6L3– Multi-DeckApplication:35CASE DATA 04 06 08 12Anti-Sweat Amps NA NA NA NAFan Amps PSC 0.37 0.52 0.74 1.11Light Amps (Two rows canopy) 0.50 0.80 1.00 1.50Defrost Load Amps None None None None# Defrosts Required 3 3 3 3BTU Req. @ +30 °F(unlighted shelves) 5400 8100 10800 16200BTU Req. @ +27°F(lighted shelves) 5820 8750 11640 17460NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.electrical data based on 115V and unlighted shelves. Add 0.063 amps per foot fornose light and .25 amps per shelf for lighted shelves.Defrost Per Day Fail Safe TerminationOff Cycle 3 40 min 48°Hot gas 3 20 Min 48°AllDischarge Air VelocityDischarge Air Temp250 FPM32°F (Lit) +34°F (unlit)Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 05


QM2AG3– Multi-DeckApplication:36CASE DATA 06 08 12Anti-Sweat Amps NA NA NAFan Amps .70 .79 1.05Light Amps (Two rows canopy) .80 1.00 1.50Defrost Load Amps (If elec-230V) 5.61 7.93 11.54# Defrosts Required 3 3 3Evaporator Temperature °F +24° +24° +24°BTU Requirements 5610 7480 11220NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lightedshelves, please add 98 BTU and .25 amps per shelf.Defrost Per Day Fail Safe TerminationOff Cycle 3 35 min 48°Hot gas 3 18 min 48°Electric 3 30 min 48°Discharge Air Velocity250 FPMDischarge Air Temp 29°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


QM3AG3– Multi-DeckApplication:37CASE DATA 04A 06A 08A 12AAnti-Sweat Amps N/A N/A N/A N/AFan Amps (SP) 0.35 0.70 0.70 1.05Light Amps (2 rows) 0.50 0.80 1.00 1.50Defrost Load Amps (If elec-230V) 3.30 5.61 7.93 11.54# Defrosts Required 4 4 4 4Evaporator Temperature °F +24° +24° +24° +24°BTU Requirements 3752 5628 7504 11256NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lighted shelves,Defrost Per Day Fail Safe TerminationOff Cycle 4 35 min 48°Hot gas 4 20 min 48°Electric 4 35 min 48°Discharge Air Velocity250 FPMDischarge Air Temp 29°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 2006


QM4A3 – Multi-DeckApplication:38CASE DATA 04A 06A 08A 12AAnti-Sweat Amps N/A N/A N/A N/AFan Amps (SP) 0.52 0.70 1.04 1.56Light Amps 0.25 0.40 0.50 0.75Defrost Load Amps (If elec-230V) 3.30 5.61 7.94 11.54# Defrosts Required 4 4 4 4Evaporator Temperature °F +24° +24° +24° +24°BTU Requirements 4880 7320 9760 14640NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lighted shelves,please add 98 BTU and .25 amps per shelf. Add 0.063 amps per foot for noseDefrost Per Day Fail Safe TerminationOff cycle 4 35 min 48°Hot gas 4 20 min 48°Electric 4 35 min 48°Discharge Air Velocity225 FPMDischarge Air Temp 29°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


QM4ALG3 – Multi-DeckApplication:40CASE DATA 04A 06A 08A 12AAnti-Sweat Amps N/A N/A N/A N/AFan Amps (SP) .52 .70 1.04 1.56Light Amps (two rows) .50 .80 1.00 1.50Defrost Load Amps (If elec-230V) 3.30 5.61 7.94 11.54# Defrosts Required 4 4 4 4Evaporator Temperature °F +24° +24° +24° +24°BTU Requirements 4880 7320 9760 14640NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lighted shelves,Defrost Per Day Fail Safe TerminationOff cycle 4 35 min 48°Hot gas 4 20 min 48°Electric 4 35 min 48°Discharge Air Velocity225 FPMDischarge Air Temp 29°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


QM53 – Multi-DeckApplication:41CASE DATA 06 08 12Anti-Sweat Amps N/A N/A N/AFan Amps (SP) 0.70 1.04 1.56Light Amps (two rows) 0.80 1.00 1.50Defrost Load Amps (If elec-230V) 5.61 7.94 11.54# Defrosts Required 3 3 3Evaporator Temperature °F +23° +23° +23°BTU Requirements 8370 11160 16740NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lightedshelves, please add 98 BTU and .25 amps per shelf.Defrost Per Day Fail Safe TerminationOff Cycle 3 35 min 48°Hot gas 3 20 min 48°Electric 3 35 min 48°Discharge Air Velocity 225 FPMDischarge Air Temp 29°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


QM5G3 – Multi-DeckApplication:42CASE DATA 04 06 08 12Anti-Sweat Amps N/A N/A N/A N/AFan Amps (SP) .52 .70 1.04 1.56Light Amps (Two rows canopy) .50 .80 1.00 1.50Defrost Load Amps (If elec-230V) 3.30 5.61 7.93 11.54# Defrosts Required 3 3 3 3Evaporator Temperature °F +23° +23° +23° +23°BTU Requirements 5580 8370 11160 16740NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lightedshelves, please add 98 BTU and .25 amps per shelf.Defrost Per Day Fail Safe TerminationOff Cycle 3 35 min 48°Hot gas 3 20 min 48°Electric 3 35 min 48°Discharge Air Velocity 225 FPMDischarge Air Temp 29°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


L5FA3– Multi-Deck FrozenApplication:43CASE DATA 04-N 06-N 08-N 12-NAnti-Sweat Amps 2.80 3.80 5.40 8.40Fan Amps 1.40 2.50 2.80 3.30Light Amps (2-rows & nose) 0.75 1.20 1.50 2.25Defrost Load Amps (If electric) 8.70 10.22 13.60 20.40# Defrosts Required 6 6 6 6Evaporator Temperature °F -20° -20° -20° -20°BTU Requirements - L5A3 7200 9050 12100 18100BTU Requirements - L5FA3 7950 10600 15900NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 6 30 min 55°Air 6 60 min 45°Hot Gas 6 30 min 60°Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths that are UL approved.Issue: Sept – 06


Specialty Cases44


B33– Specialty BakeryApplication:45CASE DATA 04 06 08 12Anti-Sweat Amps NA NA NA NAFans/Amps .53 .53 1.06 1.59Light Amps (one row canopy) .30 .51 .63 .92Defrost Load Amps None None None None# Defrosts Required 4 4 4 4Evaporator Temperature °F +20° +20° +20° +20°BTU Requirements 4000 6000 8000 12000NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lighted shelves, pleaseadd 98 BTU and .25 amps per shelf. Add 0.063 amps per foot for nose light.Defrost Per Day Fail Safe TerminationOff Cycle 4 40 min 55°Discharge Air VelocityDischarge Air Temp 33°300 FPMType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


B33– Specialty BakeryApplication:46CASE DATA 08 12Anti-Sweat Amps NA NAFans/Amps 1.06 1.59Light Amps (two row ) 0.92 1.48Defrost Load Amps None None# Defrosts Required 4 4Evaporator Temperature °F +20° +20°BTU Requirements 8000 12000NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves.Defrost Per Day Fail Safe TerminationOff Cycle 4 40 min 55°Discharge Air Velocity 300 FPMDischarge Air Temp 33°Type I refrigerator, intended for use in an area where the environmentalconditions are controlled and maintained such that conditions do notexceed 75 deg F and 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whosepolicy is one of continuous improvement, reserves the right to change atany time, specifications, design or prices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


B723– Specialty BakeryApplication:47CASE DATA 04 06 08 12Anti-Sweat Amps NA NA NA NAFan Amps .53 1.06 1.59 2.12Light Amps (Two rows canopy) .46 .92 .92 1.48Defrost Load Amps None None None None# Defrosts Required 4 4 4 4Evaporator Temperature °F +15° +15° +15° +15°BTU Requirements 6180 9270 12,360 18,540NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lightedshelves, please add 98 BTU and .25 amps per shelf. Add 0.063 ampsper foot for nose light.Defrost Per Day Fail Safe TerminationOff Cycle 4 40 min 55°Discharge Air Velocity250 - 275 FPMDischarge Air Temp 24 - 28°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 2006


PZ2AG3 – SpecialtyApplication: Pizza Merchandiser48CASE DATA 04 06 08 12Anti-Sweat Amps .48 .50 .37 .49Fans/Amps .53 .53 .53 1.06Light Amps (one row canopy) .29 .45 .45 .45Defrost Load Amps (If elec-230V) 3.30 5.61 7.93 11.54# Defrosts Required 4 4 4 4Evaporator Temperature °F +15° +15° +15° +15°BTU Requirements 2080 3200 4160 6240NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lighted shelves, pleaseadd 98 BTU and .25 amps per shelf.Defrost Per Day Fail Safe TerminationOff Cycle 3 40 min 45°Hot Gas 3 20 min 50°Electric 3 30 min 55°Discharge Air VelocityDischarge Air Temp °FPMType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has caselengths that are NSF approved.Issue: May - 06


PZ2VAP1 – SpecialtyFood To Go: Cold with rear dry storage49CASE DATA 04 06 08 12Anti-Sweat Amps .48 .50 .37 .49Fans/Amps .53 .53 .53 1.06Light Amps (one row canopy) .29 .45 .45 .45Defrost Load Amps (If elec-230V) 3.30 5.61 7.93 11.54# Defrosts Required 4 4 4 4Evaporator Temperature °F +15° +15° +15° +15°BTU Requirements 2200 3300 4400 6600NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lighted shelves, pleaseadd 98 BTU and .25 amps per shelf.Defrost Per Day Fail Safe TerminationOff Cycle 4 40 min 55°Discharge Air Velocity FPMDischarge Air Temp °Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 2006


PZ2VAP1 – SpecialtyFood To Go: Cold with refri. rear storage50CASE DATA 04 06 08 12Anti-Sweat Amps .48 .50 .37 .49Fans/Amps .53 .53 .53 1.06Light Amps (one row canopy) .29 .45 .45 .45Defrost Load Amps (If elec-230V) 3.30 5.61 7.93 11.54# Defrosts Required 4 4 4 4Evaporator Temperature °F +15° +15° +15° +15°BTU Requirements 2200 3300 4400 6600BTU for RSCN3NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lighted shelves, pleaseadd 98 BTU and .25 amps per shelf.Defrost Per Day Fail Safe TerminationOff Cycle 4 40 min 55°Discharge Air Velocity FPMDischarge Air Temp °Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 06


PZ2VAP1 – SpecialtyFood To Go: Hot Option51CASE DATA 04 06 08 12Anti-Sweat Amps .48 .50 .37 .49Fans/Amps .53 .53 .53 1.06Light Amps (one row canopy) .29 .45 .45 .45Defrost Load Amps (If elec-230V) 3.30 5.61 7.93 11.54# Defrosts Required 4 4 4 4Evaporator Temperature °F +15° +15° +15° +15°BTU Requirements 2200 3300 4400 6600NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lighted shelves, pleaseadd 98 BTU and .25 amps per shelf. The light amps don’t include heat lamps or the hotplateDefrost Per Day Fail Safe TerminationOff Cycle 4 40 min 55°Discharge Air VelocityDischarge Air Temp 33°300 FPMType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 06


PZ2VAP1 – SpecialtyFood To Go: Over & Under Merchandiser52CASE DATA 04 06 08Anti-Sweat Amps .48 .50 .37Fan Amps .53 .53 .53Light Amps (two rows) .46 ..92 .92Dome Amps (lights, fans, & Anti-sweat) 1.8 2.5 3.6# Defrosts Required 3 3 3Evaporator Temperature °F +20° +20° +20°BTU Requirements 4100 6150 8200NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lightedshelves, please add 98 BTU and .25 amps per shelf.Defrost Per Day Fail Safe TerminationOff Cycle 3 36 min 50°Discharge Air Velocity 200 FPMDischarge Air Temp 28 F°Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 06


VPA/KN-950B SpecialtyApplication:53CASE DATA 4’ 8’Anti-Sweat Amps 0.50 1.10Fan Amps 0.70 1.05Light Amps 0.24 0.47Defrost Load Amps (If electric) NA NA# Defrosts Required 4 4Evaporator Temperature °F 15°F 15°FBTU Requirements 3200 6400NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationOff Cycle 4 45 min 55°Super Heat 6-8Discharge Air Temp 24-26Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 06


VPA/KN-950A SpecialtyApplication:54CASE DATA 4’ 8’Anti-Sweat Amps 0.50 1.10Fan Amps 0.70 1.05Light Amps 0.24 0.47Defrost Load Amps (If electric) NA NA# Defrosts Required 4 4Evaporator Temperature °F 15°F 15°FBTU Requirements 3200 6400NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationOff Cycle 4 45 min 55°Super Heat 6-8Discharge Air Temp 24-26Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 2006


VPA/KN-950A SpecialtySushi Option55CASE DATA 4’ 8’Anti-Sweat Amps 0.50 1.10Fan Amps 0.70 1.05Light Amps 0.24 0.47Defrost Load Amps (If electric) NA NA# Defrosts Required 4 4Evaporator Temperature °F 15°F 15°FBTU Requirements 3200 6400NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationOff Cycle 4 45 min 55°Super Heat 6-8Discharge Air Temp 24-26Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 06


S1AG3 – SpecialtyApplication:56CASE DATA 04 06 08 12Anti-Sweat Amps 1.00 1.44 1.07 1.71Fan Amps .53 1.06 1.06 1.59Light Amps None None None NoneDefrost Load Amps (If elec-230V) 3.30 5.61 7.93 11.54# Defrosts Required 3 3 3 3BTU Requirements at +20 °F 3560 5340 7120 10,680BTU Requirements at +15 3880 5820 7760 11,640NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lighted shelves, pleaseDefrost Per Day Fail Safe TerminationOff Cycle 3 40 min 55°Hot gas 3 18 min 55°Electric 3 30 min 55°Discharge Air Velocity210 - 225 FPMDischarge Air Temp 28 - 33°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


P543– SpecialtyApplication:57CASE DATA 4’ 6’ 8’ 12’Anti-Sweat Amps 1.10 1.03 .89 1.29Fan Amps .37 .74 1.11 1.48Light Amps .29 .39 .46 .74Defrost Load Amps (If elec-230V) 3.30 5.61 7.93 11.54# Defrosts Required 4 4 4 4BTU Req. @ +20°F (Produce) 4400 6600 8800 13200BTU Req. @ +15°F (Deli) 4700 7050 9400 14100NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lighted shelves,please add 98 BTU and .25 amps per shelf. Add 0.063 amps per foot fornose light.Defrost Per Day Fail Safe TerminationOff Cycle 4 40 min 55°Hot gas 4 18 min 55°Electric 4 30 min 55°Discharge Air Velocity250 - 300 FPMDischarge Air Temp 22 - 26°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 2006


M54G3– SpecialtyApplication:58CASE DATA 04 06 08 12Anti-Sweat Amps 1.10 1.03 .89 1.29Fan Amps .37 .74 1.11 1.48Light Amps .29 .39 .46 .74Defrost Load Amps (If elec-230V) 3.30 5.61 7.93 11.54# Defrosts Required 4 4 4 4Evaporator Temperature °F +15° +15° +15° +15°BTU Requirements 4000 6000 8000 12000NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lightedshelves, please add 98 BTU and .25 amps per shelf.Defrost Per Day Fail Safe TerminationOff Cycle 4 40 min 55°Hot gas 4 18 min 55°Electric 4 30 min 55°Discharge Air Velocity250 - 300 FPMDischarge Air Temp 22 - 26°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths that are UL approved.Issue: Sept - 06


M3AV3– SpecialtyApplication:59CASE DATA 04 06 08 12Anti-Sweat Amps .52 .80Fan Amps .37 .74 1.11 1.48Light Amps (Two rows canopy) .46 .92 .92 1.48Defrost Load Amps (If elec-230V) 3.30 5.61 7.93 11.54# Defrosts Required 4 4 4 4Evaporator Temperature °F +15° +15° +15° +15°BTU Requirements 4000 6000 8000 12000NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lightedshelves, please add 98 BTU and .25 amps per shelf.Defrost Per Day Fail Safe TerminationOff Cycle 4 40 min 55°Hot gas 4 18 min 55°Electric 4 30 min 55°Discharge Air Velocity 250 - 300 FPMDischarge Air Temp 22 - 26°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has caselengths that are NSF approved.Issue: Sept - 06


M60AG3– SpecialtyApplication:60CASE DATA 04 06 08 12Anti-Sweat Amps 1.03 0.89 1.29Fan Amps .37 .74 1.11 1.48Light Amps (Two rows canopy) .46 .92 .92 1.48Defrost Load Amps (If elec-230V) 3.30 5.61 7.93 11.54# Defrosts Required 4 4 4 4Evaporator Temperature °F +15° +15° +15° +15°BTU Requirements 4000 6000 8000 12000NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lightedshelves, please add 98 BTU and .25 amps per shelf.Defrost Per Day Fail Safe TerminationOff Cycle 4 40 min 55°Hot gas 4 18 min 55°Electric 4 30 min 55°Discharge Air Velocity 250 - 300 FPMDischarge Air Temp 22 - 26°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has caselengths that are NSF approved.Issue: Sept - 2006


M72G3– SpecialtyApplication:61CASE DATA 04 06 08 12Anti-Sweat Amps 0.30 0.61 0.52 1.20Fan Amps .53 1.06 1.59 2.12Light Amps (Two rows canopy) .46 .92 .92 1.48Defrost Load Amps (If elec-230V) 3.30 5.61 7.93 11.54# Defrosts Required 4 4 4 4Evaporator Temperature °F +15° +15° +15° +15°BTU Requirements 6200 9300 12,400 18,600NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lightedDefrost Per Day Fail Safe TerminationOff Cycle 4 40 min 55°Electric 4 30 min 55°Hot Gas 4 18 min 55°Discharge Air Velocity250 - 275 FPMDischarge Air Temp 24 - 26°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


M4N3 – SpecialtyApplication:62CASE DATA 04 06 08 12Anti-Sweat Amps N/A N/A N/A N/AFan Amps .53 .53 1.06 1.59Light Amps (two rows) .86 .86 .92 1.48Defrost Load Amps (If elec-230V) 3.30 5.61 7.94 11.54# Defrosts Required 4 4 4 4Evaporator Temperature °F +20° +20° +20° +20°BTU Requirements 5500 8250 11000 16500NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.All electrical data based on 115V and unlighted shelves. For lightedshelves, please add 98 BTU and .25 amps per shelf.Defrost Per Day Fail Safe TerminationOff cycle 4 40 min 55°Hot gas 4 18 min 55°Electric 4 30 min 55°Discharge Air Velocity FPMDischarge Air Temp °FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 2006The above case model, has caselengths that are NSF approved.


Glass Door Cases63


QDV5V34– Glass Door - EliminatorApplication:64CASE DATA - # of Doors 02 dr 03 dr 04 dr 05 drAnti-Sweat Amps .71 1.17 1.37 1.67Fan Amps (SP) 0.70 1.05 1.40 1.75Fan Amps (PSC) 0.44 O.66 O.88 1.10Light Amps 1.39 1.80 2.32 2.79Defrost Load Amps None None None None# Defrosts Required 1 1 1 1Evaporator Temperature °F +28° +28° +28° +28°* BTU Requirements 1700 2550 3400 4250NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.* Deduct 30 BTU/Door for PSC motors.Defrost Per Day Fail Safe TerminationOff Cycle 1 30 min 40°Discharge Air VelocityDischarge Air Temp 36°250 FPMType I refrigerator, intended for use in an area where the environmentalconditions are controlled and maintained such that conditions do notexceed 75 deg F and 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policyis one of continuous improvement, reserves the right to change at anytime, specifications, design or prices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


QDV5V34– Glass Door—StandardApplication:65CASE DATA - # of Doors 02 dr 03 dr 04 dr 05 drAnti-Sweat Amps .85 1.28 1.71 2.13Fan Amps (SP) 0.70 1.05 1.40 1.75Fan Amps (PSC) 0.44 0.66 0.88 1.10Light Amps 1.39 1.80 2.32 2.79Defrost Load Amps None None None None# Defrosts Required 1 1 1 1Evaporator Temperature °F +28° +28° +28° +28°*BTU Requirements 1800 2700 3600 4500NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.* Deduct 30 BTU/Door for PSC motors.Defrost Per Day Fail Safe TerminationOff Cycle 1 30 min 40°Discharge Air VelocityDischarge Air Temp 36°250 FPMType I refrigerator, intended for use in an area where the environmentalconditions are controlled and maintained such that conditions do notexceed 75 deg F and 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policyis one of continuous improvement, reserves the right to change at anytime, specifications, design or prices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


QDV5V14 – Glass Door MCUApplication:66208V Circuit <strong>Data</strong> 2M Door 3M DoorCompressor RLA 4.20 5.70Compressor LRA 16.80 24.10Condenser Fan Motor Amps 0.70 0.70Defrost Heaters Amps NA NAMinimum Circuit Ampacity 5.90 8.10Maximum Overcurrent Protection 15 15Power Supply 208/1/60 208/1/60Horse Power 1/3 1/2Defrost Per Day Fail Safe TerminationElectric 1 30 min 40°Discharge Air Velocity 250 FPMDischarge Air Temp +32°FMaintained Temperature +38°F120V Circuit <strong>Data</strong> 2M Door 3M DoorAnti-Sweat Amps 0.74 1.22Evap Fan Motor Amps 0.46 0.69Light Amps 1.45 1.88Drain Pan Heater NA NACondensate Pump Amps 0.94 0.94Condensate Evaporator Amps 8.30 8.30Minimum Circuit Ampacity 12.13 13.27Maximum Overcurrent Protection 15 15Power Supply 120/1/60 120/1/60Refrigerant R404A R404A?The above case model, has case lengths thatare UL and NSF approved.Issue: March - 06


QIV5V14– Glass Door MCUApplication:67208V Circuit <strong>Data</strong> 2M Door 3M DoorCompressor RLA 9.6 11.4Compressor LRA 59.2 59.2Condenser Fan Motor Amps 0.85 2.6Defrost Heaters Amps 6.09 9.13Minimum Circuit Ampacity 13.2 17.2Maximum Overcurrent Protection 20 25Power Supply 208/1/60 208/1/60Horse Power 1 2Defrost Per Day Fail Safe TerminationElectric 1 50 min 65°Discharge Air Velocity 250 FPMDischarge Air Temp -5/-12°FMaintained Temperature 0°F120V Circuit <strong>Data</strong> 2M Door 3M DoorAnti-Sweat Amps 2.53 3.46Evap Fan Motor Amps 0.46 0.69Light Amps 1.45 1.88Drain Pan Heater 0.41 0.68Condensate Pump Amps 0.94 0.94Condensate Evaporator Amps 8.30 8.30Minimum Circuit Ampacity 14.33 16.19Maximum Overcurrent Protection 15 20Power Supply 120/1/60 120/1/60Refrigerant R404A R404A?The above case model, has case lengths thatare UL and NSF approved.Issue: March - 06


QLV5V34– Glass Door - Eliminator - FFQIV5V34– Glass Door—Eliminator - ICApplication:68CASE DATA - # of Doors 02-UN 03-UN 04-UN 05-UNAnti-Sweat Amps 2.43 3.32 4.40 5.44Fan Amps .88 1.32 1.76 2.20Light Amps 1.39 1.80 2.32 2.79Drain Heater Amps. 0.39 0.65 0.91 1.17Defrost Load Amps @ 230V 6.73 10.10 13.46 16.83# Defrosts Required 1 1 1 1BTU Requirements @ -10°F 2500 3750 5000 6250BTU Requirements @ -17°F 2640 3960 5280 6600NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 1 60 min 55°Discharge Air Velocity 250 FPMDischarge Air Temp -5/-12 F°Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 2006


QLV5V34– Glass Door—Standard FFQIV5V34– Glass Door—Standard ICApplication:69CASE DATA - # of Doors 02 dr 03 dr 04 dr 05 drAnti-Sweat Amps 3.67 4.73 6.25 7.69Fan Amps .88 1.32 1.76 2.20Light Amps 1.39 1.80 2.32 2.79Drain Heater Amps. 0.39 0.65 0.91 1.17Defrost Load Amps @ 230V 6.73 10.10 13.46 16.83# Defrosts Required 1 1 1 1BTU @ -11°F (Frozen Food) 2750 4125 5500 6875BTU @ -18°F (Ice Cream) 2920 4380 5840 7300NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 1 60 min 55°Discharge Air Velocity250 FPMDischarge Air Temp -5/-12 F°Type I refrigerator, intended for use in an area where the environmentalconditions are controlled and maintained such that conditions do notexceed 75 deg F and 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policyis one of continuous improvement, reserves the right to change at anytime, specifications, design or prices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


QLV6V34– Glass Door Eliminator - FFQIV6V34– Glass Door Eliminator - ICApplication:70CASE DATA - # of Doors 02-DR 03-DR 04-DR 05-DRAnti-Sweat Amps 2.43 3.32 4.40 5.44Fan Amps (PSC) 0.44 0.66 0.88 1.10Light Amps 1.39 1.80 2.32 2.79Drain Heater Amps. 0.39 0.65 0.91 1.17Defrost Load Amps @ 230V 6.73 10.10 13.46 16.83# Defrosts Required 1 1 1 1BTU Req. @ -11°F for FF 2605 3908 5210 6513BTU Req. @ -18°F for IC 2751 4126 5502 6877NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 1 60 min 65°Hotgas 1 34 min 65Discharge Air Velocity 250 FPMDischarge Air Temp -5/-12 F°Type I refrigerator, intended for use in an area where the environmentalconditions are controlled and maintained such that conditionsdo not exceed 75 deg F and 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>,whose policy is one of continuous improvement, reserves the right tochange at any time, specifications, design or prices without incurringobligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 2006


QLV6V34– Glass Door—Standard FFQIV6V34– Glass Door—Standard ICApplication:71CASE DATA - # of Doors 02-DR 03-DR 04-DR 05-DRAnti-Sweat Amps 3.67 4.73 6.13 7.69Fan Amps (PSC) 0.44 0.66 0.88 1.10Light Amps 1.39 1.80 2.32 2.79Drain Heater Amps. 0.39 0.65 0.91 1.17Defrost Load Amps @ 230V 6.73 10.10 13.46 16.83# Defrosts Required 1 1 1 1BTU Req. @ -12°F for FF 2865 4298 5731 7164BTU Req. @ -19°F for IC 3043 4564 6085 7607NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 1 60 min 65°Hotgas 1 34 min 65Discharge Air Velocity 250 FPMDischarge Air Temp -5/-12 F°Type I refrigerator, intended for use in an area where the environmentalconditions are controlled and maintained such that conditionsdo not exceed 75 deg F and 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>,whose policy is one of continuous improvement, reserves the right tochange at any time, specifications, design or prices without incurringobligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


NGCEI – Glass Door—StandardApplication:7202 Dr 03 Dr 04 Dr 05 DrAnti-Sweat Amps 1.74 2.42 3.22 3.91Fan Amps .88 1.32 1.76 2.20Light Amps (Anthony Drs) 1.39 1.80 2.32 2.79Defrost Load Amps NA NA NA NA# Defrosts Required (if electric) 3 3 3 3Evaporator Temperature °F +20° +20° +20° +20°BTU Requirements +20° F 2720 4030 5440 6300NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 3 44 55°Med. Temp.Discharge Air Velocity275 - 325 FPMDischarge Air Temp 34-38Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 06


QFGCEI – Glass Door - StandardApplication:7302 Dr 03 Dr 04 Dr 05 DrAnti-Sweat Amps 3.63 5.25 7.02 8.61Fan Amps 0.70 1.05 1.40 1.75Light Amps (Anthony Drs) 1.39 1.80 2.32 2.79Drain Heater Amps. 0.39 0.65 0.91 1.17Defrost Load Amps (If elec-230V) 6.73 10.10 13.46 16.83# Defrosts Required (if electric) 1 1 1 1Evaporator Temperature °F-10 FF-17 IC-10° FF-17° IC-10° FF-17° IC-10° FF-17° ICBTU Requirements2750 FF2850 IC4125 FF4275 IC5500 FF5700 IC6875 FF7125 ICNOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 1 45 min 65°Hotgas 1 34 min 65°Frozen FoodIce CreamDischarge Air Velocity 275 - 325 FPM 275 - 325 FPMDischarge Air Temp -4° -11°Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: September - 05


QFGCEI – Glass Door - EliminatorApplication:7402 Dr 03 Dr 04 Dr 05 DrAnti-Sweat Amps 1.92 2.81 3.60 4.45Fan Amps .70 1.05 1.40 1.75Light Amps (Anthony Drs) 1.39 1.80 2.32 2.79Drain Heater Amps. 0.39 0.65 0.91 1.17Defrost Load Amps (If elec-230V)) 6.73 10.10 13.46 16.83# Defrosts Required 1 1 1 1Evaporator Temperature °F-10 FF-17 IC-10° FF-17° IC-10° FF-17° IC-10° FF-17° ICBTU Requirements2400 FF2500 IC3600 FF3750 IC4800 FF5000 IC6000 FF6250 ICNOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 1 45 65°Hotgas 1 34 65°Frozen FoodIce CreamDischarge Air Velocity 250 FPM 250 FPMDischarge Air Temp -4 -11Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


QFGCEID – Glass Door EliminatorApplication:7504 Dr 06 Dr 08 Dr 10 DrAnti-Sweat Amps 3.94 5.62 7.20 8.90Fan Amps 4/.1.40 6/2.10 8/2.80 10/3.50Light Amps (Anthony Drs) 2.78 3.60 4.64 5.58Drain Heater Amps. 0.78 1.30 1.82 2.34Defrost Load Amps (If elec-230V) 13.46 20.20 26.92 33.66# Defrosts Required 1 1 1 1Evaporator Temperature °F-10 FF-17 IC-10° FF-17° IC-10° FF-17° IC-10° FF-17° ICBTU Requirements4200 FF4400 IC6300 FF6600 IC8400 FF8800 IC10500FF11000 ICNOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 1 45 65°Hotgas 1 34 65°Frozen FoodIce CreamDischarge Air Velocity 250 FPM 250 FPMDischarge Air Temp -4° -11°Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: September - 05


FGCEID – Glass Door StandardApplication:7604 Dr 06 Dr 08 Dr 10 DrAnti-Sweat Amps 7.34 9.46 12.50 15.38Fan Amps 4/.1.76 6/2.64 8/3.52 10/4.40Light Amps (Anthony Drs) 4.04 5.20 6.64 7.80Drain Heater Amps. 0.78 1.30 1.82 2.34Defrost Load Amps (If elec-230V) 13.46 20.20 26.92 33.66# Defrosts Required 1 1 1 1Evaporator Temperature °F-11 FF-18 IC-11° FF-18° IC-11° FF-18° IC-11° FF-18° ICBTU Requirements5226 FF5606 IC7840 FF8320 IC11100 FF11680 IC13060FF13870 ICNOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 1 60 55°Frozen FoodIce CreamDischarge Air Velocity 275-325 FPM 275-325 FPMDischarge Air Temp -5° -10°Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


FGCEIDS-4 – Glass DoorApplication: 8 Door End Cap77Std. Door Elm. DoorAnti-Sweat Amps 14.04 7.98Fan Amps 2.88 2.88Light Amps (Anthony Drs) 6.64 6.64Drain Heater Amps. 2.34 1.80Defrost Load Amps (If elec-230V) 26.92 26.92# Defrosts Required 1 1Evaporator Temperature °F -13 FF -11° FFBTU Requirements 9800 FF 8167 FFNOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 1 60 65°Hot Gas 1 34 65°Type I refrigerator, intended for use in an area where the environmentalconditions are controlled and maintained such that conditions do notexceed 75 deg F and 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whosepolicy is one of continuous improvement, reserves the right to change atany time, specifications, design or prices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has caselengths that are NSF approved.Issue: Sept - 2006


Island Cases78


P1W3– Island ProduceApplication:79CASE DATA 04 06 08 10 12Anti-Sweat Amps NA NA NA NA NAFan Amps .68 1.36 1.36 2.04 2.04Light Amps NA NA NA NA NADefrost Load Amps None None None None None# Defrosts Required 4 4 4 4 4Evaporator Temperature °F +20° +20° +20° +20° +20°BTU Requirements 3820 5730 7640 9550 11460NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationOff Cycle 4 40 min 55°Discharge Air Velocity200 – 250 FPMDischarge Air Temp 34 - 40°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


P1W3– Island Produce80Issue: March - 06


EP1W3– Island End CapApplication:81CASE DATAEP1W3Anti-Sweat AmpsNAFan Amps .34Light AmpsN/ADefrost Load AmpsNone# Defrosts Required 4Evaporator Temperature °F +20°BTU Requirements 2860NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationOff Cycle 4 40 min 55°Discharge Air Velocity130 – 175 FPMDischarge Air Temp 34 - 40°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


EP543– Island End CapApplication:82CASE DATAEnd CaseAnti-Sweat Amps .20Fan Amps 2/1.11Light AmpsDrain Heater Amps. 0.48Defrost Load AmpsNone# Defrosts Required 4Evaporator Temperature °F +20°BTU Requirements 9400NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.*There is .25 amps per shelfDefrost Per Day Fail Safe TerminationOff Cycle 4 40 min 55°Discharge Air Velocity FPMDischarge Air Temp °Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


EP543 Island layout withP543’s Back to Back83Issue: September - 05


EC54G3– Island End CapApplication:84CASE DATAEnd CaseAnti-Sweat Amps .20Fan Amps 1.11Light AmpsDrain Heater Amps. 0.48Defrost Load AmpsNone# Defrosts Required 4Evaporator Temperature °F +20°BTU Requirements 9400NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.*There is .25 amps per shelfDefrost Per Day Fail Safe TerminationOff Cycle 4 40 min 55°Discharge Air Velocity FPMDischarge Air Temp °Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 06


EC54G3 Island Layout with85Issue: March - 06


EC32G1 Island Layout with86Issue: March - 06


C1WI3– Single Deck IslandApplication:87CASE DATA 08 12Anti-Sweat Amps 1.81 2.23Fan Amps 1.22 1.22Light Amps (Two rows canopy) N/A N/ADefrost Load Amps (If elec-230V) 11.30 14.80# Defrosts Required 4 4Evaporator Temperature °F +20° +20°BTU Requirements 8800 13200NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 4 40 min 55°Hot gas 4 20 min 55°Discharge Air Velocity 270 - 425 FPMDischarge Air Temp 32 - 38°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has caselengths that are NSF approved.Issue: Sept - 2006


C1NVI1– Single Deck IslandApplication:88CASE DATA 08-N 12-NAnti-Sweat Amps 1.81 2.23Fan Amps 1.22 1.22Light Amps (Two rows canopy) N/A N/ADefrost Load Amps (If elec-230V) 11.30 14.80# Defrosts Required 4 4Evaporator Temperature °F +20° +20°BTU Requirements 8800 13200NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 4 40 min 55°Hot gas 4 20 min 55°Discharge Air Velocity 270 - 425 FPMDischarge Air Temp 32 - 38°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has caselengths that are NSF approved.Issue: Sept - 2006


C1VI3– Single Deck IslandApplication:89CASE DATA 08 12Anti-Sweat AmpsFan Amps 1.06 2.12Light Amps (Two rows canopy) 1.91 3.46Defrost Load Amps (If elec-230V) 11.30 14.80# Defrosts Required 4 4Evaporator Temperature °F +15° +15°BTU RequirementsNOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.*There is .25 amps per shelfDefrost Per Day Fail Safe TerminationElectric 6 30 min 55°Discharge Air Velocity FPMDischarge Air Temp 31°Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has caselengths that are NSF approved.Issue: Sept - 06


C1VI3– Single Deck IslandWith Straight glass:90CASE DATA 08 12Anti-Sweat AmpsFan Amps 1.06 2.12Light Amps (Two rows canopy) 1.91 3.46Defrost Load Amps (If elec-230V) 11.30 14.80# Defrosts Required 4 4Evaporator Temperature °F +15° +15°BTU RequirementsNOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.*There is .25 amps per shelfDefrost Per Day Fail Safe TerminationElectric 6 30 min 55°Discharge Air Velocity FPMDischarge Air Temp 31°Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has caselengths that are NSF approved.Issue: Sept - 2006


C2VI3– Multi-Deck Islandwith straight glass:91CASE DATA 08 12Anti-Sweat AmpsFan Amps 1.06 2.12Light Amps (Two rows canopy) 1.91 3.46Defrost Load Amps (If elec-230V) 11.30 14.80# Defrosts Required 4 4Evaporator Temperature °F +15° +15°BTU Requirements 12000 18000NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.*There is .25 amps per shelfDefrost Per Day Fail Safe TerminationElectric 6 30 min 55°Discharge Air Velocity 125 FPMDischarge Air Temp 31°Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


C2VI3– Multi-Deck IslandApplication:92CASE DATA 08 12Anti-Sweat AmpsFan Amps 1.06 2.12Light Amps (Two rows canopy) 1.91 3.46Defrost Load Amps (If elec-230V) 11.30 14.80# Defrosts Required 4 4Evaporator Temperature °F +15° +15°BTU Requirements 12000 18000NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.*There is .25 amps per shelfDefrost Per Day Fail Safe TerminationElectric 6 30 min 55°Discharge Air Velocity 125 FPMDischarge Air Temp 31°Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


C2VE3– Multi-Deck IslandApplication:93CASE DATA 08 12Anti-Sweat AmpsFan AmpsLight Amps (Two rows canopy) 1.91 3.46Defrost Load Amps (If elec-230V) 11.30 14.80# Defrosts Required 4 4Evaporator Temperature °F +15° +15°BTU RequirementsNOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.*There is .25 amps per shelfDefrost Per Day Fail Safe TerminationElectric 6 30 min 55°Discharge Air VelocityDischarge Air Temp 31°125 FPMType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has caselengths that are NSF approved.Issue: Sept - 2006


M1WI3– Single Deck IslandApplication:94CASE DATA 08 12Anti-Sweat Amps 1.35 1.93Fan Amps .94 1.08Light Amps (Two rows canopy) 1.91 3.46Defrost Load Amps (If elec-230V) 11.30 14.80# Defrosts Required 4 4Evaporator Temperature °F +15° +15°BTU Requirements 8800 13200NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 4 40 min 55°Hot gas 4 20 min 55°Discharge Air Velocity270 - 425 FPMDischarge Air Temp 32 - 38°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has caselengths that are NSF approved.Issue: Sept - 2006


LD13– Island Dual TempApplication:95CASE DATA D13-5’ D13-10’ LD13-5’ LD13-10’Anti-Sweat Amps 1.52 1.81 1.52 2.65Fan Amps .34 .68 .34 .68Light Amps N/A N/A N/A N/ADefrost Load Amps (@ 230V) N/A N/A 7.83 15.65# Defrosts Required 2 2 3 3Evaporator Temperature °F +20° +20° -25° -25°BTU Requirements 2750 5500 3350 6700NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 3 30 min 55°Off-cycle 2 30 min 55°Discharge Air Velocity FPMDischarge Air Temp-15°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept – 06


QIL3– Narrow IslandApplication:96CASE DATA 06 08 12Anti-Sweat Amps 0.78 0.98 1.46Fan Amps Std. 0.70 0.70 1.05Drain Heater Amps. 0.06 0.39 0.83Light Amps N/A N/A N/ADefrost Load Amps (If elec-230V) 6.52 9.37 14.06# Defrosts Required at +24°F 3 3 3# Defrosts Required at -22°F 1 1 1BTU Requirements at +20°F 2025 2700 4050BTU Requirements at –17°F 2250 3000 4500BTU Requirements at –22°F 2400 3200 4800NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 1 60 min 48°FHot Gas 1 25 min 48°F+24°F Off Cycle 3 40 min 55°FDischarge Air VelocityDischarge Air Temp200 FPM -12°F (low temp)Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


ILG3– Narrow IslandApplication:97CASE DATA 06 08 12Anti-Sweat Amps N/A 2.82 4.25Fan Amps N/A 1.26 1.26Drain Heater Amps. 0.06 0.39 0.83Light Amps N/A N/A N/ADefrost Load Amps (If elec-230V) N/A 9.37 14.06# Defrosts Required N/A 1 1BTU Requirements at -20° N/A 4320 6480BTU Requirements at –30° N/A 4480 6720NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 1 60 55°FFrozen Food Low Temp Med. TempDischarge Air Velocity 120-130 FPM 120-130 FPM 120-130 FPMDischarge Air Temp -6°F -14°F +28°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has caselengths that are NSF approved.Issue: Sept - 2006


WIL3– Wide IslandApplication:98CASE DATA 8’ 12’Anti-Sweat Amps .98 1.46Fan Amps .94 .94Light Amps N/A N/ADrain Heater Amps 0.34 0.83Defrost Load Amps (If elec-230V) 9.37 14.06# Defrosts Required 1 1Evaporator Temperature °F -20°F -20°FBTU Requirements 4480 6720NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 1 60 min 55°Discharge Air Velocity 130 FPMDischarge Air Temp -8°FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has caselengths that are NSF approved.Issue: Sept - 2006


QWSTG– Twin IslandApplication:99CASE DATA 08 12Anti-Sweat Amps - per side 1.35 2.0Fan Amps - per side (SP) 0.68 1.02Fan Amps - per side (PSC) 0.44 0.66Drain Heater Amps-per side (Electric) 0.26 0.26Drain Heater Amps-per side (Hotgas) 0.65 1.09Def. Load Amps-per side (If elec-230V) 9.37 14.06Light Amps. N/A N/ABTU Requirements per side at +24°F 1900 2850BTU Requirements per side at –15°F 2600 3900BTU Requirements per side at –20°F 2900 4350NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.* BTU ratings are with all sides operating at the same Temperature.Defrost Per Day Fail Safe TerminationElectric 1 45 48°FHotgas 1 20 48°FFrozen Food Ice Cream DairyDischarge Air Temp -11°F -16°F +30°FDischarge Velocities 225 FPM 225 FPM 225 FPMType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: May - 06The above case model, has case lengths thatare UL and NSF approved.


QWSTGE– Island End CapApplication:100CASE DATAEnd CaseAnti-Sweat Amps 1.50Fan Amps (SP) 0.68Fan Amps (PSC) 0.44Drain Heater Amps. (Electric) 0.52Drain Heater Amps. (Hot gas) 0.39Defrost Load Amps (If elec-230V) 6.52# Defrosts Required 1BTU Requirements @ +24 °F 2225BTU Requirements @ -15 °F 3475BTU Requirements @ -20 °F 3825NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 1 45 min 48°Hotgas 1 20 min 48°Frozen Food Ice Cream DairyDischarge Air Temp -11°F -16°F +30°FDischarge Velocities 375 FPM 375 FPM 375 FPMType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: May - 06


QWST– Twin IslandApplication:101CASE DATA 08 12Anti-Sweat Amps—per side 0.98 1.46Fan Amps—per side (SP) 0.68 1.02Fan Amps—per side (PSC) 0.44 0.66Drain Heater Amps—per side (Electric) 0.26 0.26Drain Heater Amps—per side (Hot gas) 0.65 1.09Defrost Load Amps-per side (If elec-230V) 9.37 14.06Lights Amps N/A N/ABTU Requirements—per side at +24°F 1800 2700BTU Requirements—per side at –15°F 2500 3750BTU Requirements—per side at –20°F 2800 4200NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.* BTU ratings are with all sides operating at the same Temperature.Defrost Per Day Fail Safe TerminationElectric 1 45 min 48°FHotgas 1 20 min 48°FFrozen Food Ice Cream DairyDischarge Air Temp -11°F -16°F +30°FDischarge Velocities 225 FPM 225 FPM 225 FPMType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: May - 06The above case model, has case lengths thatare UL and NSF approved.


QWST– Twin IslandWith Super StructureC41 - one row of shelvesC42 - two rows of shelves102Issue: March - 06


QWSTE– Island End CapApplication:103CASE DATAEnd CaseAnti-Sweat Amps 0.94Fan Amps (SP) 0.68Fan Amps (PSC) 0.44Drain Heater Amps (Electric) 0.52Drain Heater Amps (Hot gas) 0.39Defrost Load Amps (If elec-230V) 6.52# Defrosts Required 1BTU Requirements @ +24 °F 2000BTU Requirements @ -15 °F 3250BTU Requirements @ -20 °F 3600NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationElectric 1 45 min 48°FHotgas 1 20 min 48°FFrozen Food Ice Cream DairyDischarge Air Temp -11°F -16°F +30°FDischarge Velocities 375 FPM 375 FPM 375 FPMType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: May - 06The above case model, has case lengths thatare UL and NSF approved.


QWSTGE– Integrated IslandApplication:104CASE DATA 08 12Ratings for Sections End + 2 sides End + 2 sidesAnti-Sweat Amps 1.5 + 1.10(x2) 1.5 + 1.77(x2)Fan Amps (SP) 0.68 + 0.34(x2) 0.68 + 0.68(x2)Fan Amps (PSC) 0.44+ 0.22(x2) 0.44 + 0.44(x2)Drain Heater Amps. (Electric Def.) 0.52 + 0.26(x2) 0.52 + 0.26(x2)Drain Heater Amps. (Hot gas Def.) 0.39 + 0.39(x2) 0.39 + 0.65(x2)Defrost Load Amps (If elec-230V) 6.52 + 6.52(x2) 6.52 + 9.37(x2)# Defrosts Required at +24°F 1 1* BTU Requirements at +24°F 2225 + 950(x2) 2225 + 1900(x2)* BTU Requirements at –15°F 3475 + 1300(x2) 3475 + 2600(x2)* BTU Requirements at –20°F 3825 + 1450(x2) 3825 + 2900(x2)NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.* BTU ratings are with all sides operating at the same Temperature.The above case model, has case lengths thatare UL and NSF approved.Issue: May - 06


QWSTE– Integrated IslandApplication:105CASE DATA 08 12Ratings for Sections End + 2 sides End + 2 sidesAnti-Sweat Amps 0.94 + 0.73(x2) 0.94 + 1.22(x2)Fan Amps (SP) 0.68 + 0.34(x2) 0.68 + 0.68(x2)Fan Amps (PSC) 0.44 + 0.22(x2) 0.44+ 0.44(x2)Drain Heater Amps. (Electric Def) 0.52 + 0.26(x2) 0.52 + 0.26(x2)Drain Heater Amps. (Hot gas Def) 0.39 + 0.39(x2) 0.39 + 0.65(x2)Defrost Load Amps (If elec-230V) 6.52 + 6.52(x2) 6.52 + 9.37(x2)# Defrosts Required 1 1*BTU Requirements at +24°F 2000 + 900(x2) 2000 + 1800(x2)*BTU Requirements at –15°F 3250 + 1250(x2) 3250 + 2500(x2)*BTU Requirements at –20°F 3600 + 1400(x2) 3600 + 2800(x2)The above case model, has case lengths thatare UL and NSF approved.NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.* BTU ratings are with all sides operating at the same temperature.Issue: May - 06


QWSTE– Integrated Island20’ Island Layout106CASE DATA QWSTE3-8 QWSTE3-12Ratings for Sections End + 2 sides End + 2 sidesAnti-Sweat Amps 0.94 + 0.73(x2) 0.94 + 1.22(x2)Fan Amps (SP) 0.68 + 0.34(x2) 0.68 + 0.68(x2)Fan Amps (PSC) 0.44 + 0.22(x2) 0.44 + 0.44(x2)Drain Heater Amps. (Electric Def) 0.52 + 0.26(x2) 0.52 + 0.26(x2)Drain Heater Amps. (Hot gas Def) 0.39 + 0.39(x2) 0.39 + 0.65(x2)Defrost Load Amps (If elec-230V) 6.52 + 6.52(x2) 6.52 + 9.37(x2)# Defrosts Required 1 1*BTU Requirements at +24°F 2000 + 900(x2) 2000 + 1800(x2)*BTU Requirements at –15°F 3250 + 1250(x2) 3250 + 2500(x2)*BTU Requirements at –20°F3600 + 1400(x2) 3600 + 2800(x2)NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.* BTU ratings are with all sides operating at the same temperature.Frozen Food Ice Cream DairyDischarge Air Temp -11°F -16°F +30°FQWSTE Discharge 375 FPM 375 FPM 375 FPMQWST Discharge 225 FPM 225 FPM 225 FPMDefrost Per Day Fail Safe TerminationElectric 1 45 min 48°FHotgas 1 20 min 48°FThe above case model, has case lengths thatare UL and NSF approved.


Service Cases107


VRHB-950-RP ServiceApplication:108CASE DATA 4’ 6’ 8’Anti-Sweat Amps 1.00 1.00 2.20Fan Amps 1.40 1.40 2.35Light Amps 0.24 0.47 0.47Defrost Load Amps (If electric) NA NA NA# Defrosts Required 4 4 4Evaporator Temperature °F 10°F 10°F 10°FBTU Requirements 3400 5100 6800NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationOff Cycle 4 45 min 55°Super Heat 6-8Discharge Air TempType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 2006


VFHC-950-RP ServiceApplication:109CASE DATA 4’ 8’Anti-Sweat Amps 0.50 1.10Fan Amps 1.40 2.00Light Amps 0.24 0.47Defrost Load Amps (If electric) NA NA# Defrosts Required 4 4Evaporator Temperature °F 10°F 10°FBTU Requirements 3400 6800NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationOff Cycle 4 45 min 55°Super Heat 6-8Discharge Air TempType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 2006


VFGC-950-RP Proto-type ServiceApplication:110CASE DATA 4’ 8’Anti-Sweat Amps 0.50 1.10Fan Amps NA NALight Amps 0.24 0.47Defrost Load Amps (If electric) NA NA# Defrosts Required 4 4Evaporator Temperature °F 15°F 15°FBTU RequirementsNOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationOff Cycle 4 45 min 55°Super Heat 6-8Discharge Air TempType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 06


VRM-950-12NPNL ServiceApplication:111CASE DATA 4’ 8’Anti-Sweat Amps NA NAFan Amps 0.70 1.05Light Amps NA NADefrost Load Amps (If electric) NA NA# Defrosts Required 4 4Evaporator Temperature °F 15°F 15°FBTU Requirements 2200 4400NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationOff Cycle 4 45 min 55°Super Heat 6-8Discharge Air Temp 26-28Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 06


VRM-950-12NPNL Service Flat GlassApplication:112CASE DATA 4’ 8’Anti-Sweat Amps NA NAFan Amps 0.70 1.05Light Amps NA NADefrost Load Amps (If electric) NA NA# Defrosts Required 4 4Evaporator Temperature °F 15°F 15°FBTU Requirements 2200 4400NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationOff Cycle 4 45 min 55°Super Heat 6-8Discharge Air Temp 26-28Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 06


VRM-1250-12NPNL ServiceApplication:113CASE DATA 4’ 8’Anti-Sweat Amps NA NAFan Amps 0.70 1.05Light Amps NA NADefrost Load Amps (If electric) NA NA# Defrosts Required 4 4Evaporator Temperature °F 15°F 15°FBTU Requirements 2200 4400NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationOff Cycle 4 45 min 55°Super Heat 6-8Discharge Air Temp 26-28Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 2006


NS39S1– Service Straight GlassApplication:1144’ 6’ 8’ 12’Anti-Sweat Amps None None None NoneFan Amps None None None NoneLight Amps .43 1.04 1.04 1.68Defrost Load Amps None None None None# Defrosts Required 1 1 1 1Evaporator Temperature °F +20° +20° +20° +20°BTU Requirements 1280 1920 2560 3840NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.There is .25 amps per lighted shelfDefrost Per Day Fail Safe TerminationOff Cycle 1 80 TIMEDischarge Air VelocityDischarge Air TempGravityN/AType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept — 06


NS39VL1CT– Service Lift GlassApplication:1154’ 6’ 8’ 12’Anti-Sweat Amps None None None NoneFan Amps None None None NoneLight Amps .86 1.72 1.52 2.64Defrost Load Amps None None None None# Defrosts Required 1 1 1 1Evaporator Temperature °F +20° +20° +20° +20°BTU Requirements 1870 2550 3400 5100NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.There is .25 amps per lighted shelfDefrost Per Day Fail Safe TerminationOff Cycle 1 80 TIMEDischarge Air VelocityDischarge Air TempGravityN/AType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


NS39V1– Service Curve GlassApplication:1164’ 6’ 8’ 12’Anti-Sweat Amps None None None NoneFan Amps None None None NoneLight Amps .43 1.04 1.04 1.68Defrost Load Amps None None None None# Defrosts Required 1 1 1 1Evaporator Temperature °F +20° +20° +20° +20°BTU Requirements 1280 1920 2560 3840NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.There is .25 amps per lighted shelfDefrost Per Day Fail Safe TerminationOff Cycle 1 80 TIMEDischarge Air VelocityDischarge Air TempGravityN/AType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 2006


NS39V1– Double Curve Fix GlassApplication:1174’ 6’ 8’ 12’Anti-Sweat Amps None None None NoneFan Amps None None None NoneLight Amps .43 1.04 1.04 1.68Defrost Load Amps None None None None# Defrosts Required 1 1 1 1Evaporator Temperature °F +20° +20° +20° +20°BTU Requirements 1280 1920 2560 3840NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.There is .25 amps per lighted shelfDefrost Per Day Fail Safe TerminationOff Cycle 1 80 TIMEDischarge Air VelocityDischarge Air TempGravityN/AType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


VRM-950-12RP ServiceApplication:118CASE DATA 4’ 8’Anti-Sweat Amps .50 1.10Fan Amps .70 1.05Light Amps .24 .47Defrost Load Amps (If electric) NA NA# Defrosts Required 4 4Evaporator Temperature °F 20°F 20°FBTU Requirements 2000 4000NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationOff Cycle 4 45 min 55°Super Heat 6-8Discharge Air Temp 26-28Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 06


VRM-950-12RP Service NW GlassApplication:119CASE DATA 4’ 8’Anti-Sweat Amps .50 1.10Fan Amps .70 1.05Light Amps .24 .47Defrost Load Amps (If electric) NA NA# Defrosts Required 4 4Evaporator Temperature °F 20°F 20°FBTU Requirements 2000 4000NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationOff Cycle 4 45 min 55°Super Heat 6-8Discharge Air Temp 26-28Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 2006


VRMB-950-RP ServiceApplication:120CASE DATA 4’ 8’Anti-Sweat Amps 0.50 1.10Fan Amps 1.40 2.35Light Amps 0.24 0.47Defrost Load Amps (If electric) NA NA# Defrosts Required 4 4Evaporator Temperature °F 20°F 20°FBTU Requirements 2600 5200NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationOff Cycle 4 45 min 55°Super Heat 6-8Discharge Air Temp 26-28Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 06


VFMC-950-RP ServiceApplication:121CASE DATA 4’ 8’Anti-Sweat Amps 0.50 1.10Fan Amps 1.40 2.35Light Amps 0.24 0.47Defrost Load Amps (If electric) NA NA# Defrosts Required 4 4Evaporator Temperature °F 20°F 20°FBTU Requirements 2600 5200NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.Defrost Per Day Fail Safe TerminationOff Cycle 4 45 min 55°Super Heat 6-8Discharge Air TempType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: Sept - 06


NS39SJ1– Service Straight GlassApplication:1224’ 6’ 8’ 12’Anti-Sweat Amps None None None NoneFan Amps .68 .68 1.02 1.36Light Amps .43 1.04 1.04 1.68Defrost Load Amps None None None None# Defrosts Required 1 1 1 1Evaporator Temperature °F +20° +20° +20° +20°BTU Requirements 1280 1920 2560 3840NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.There is .25 amps per lighted shelfDefrost Per Day Fail Safe TerminationOff Cycle 1 46 TIMEDischarge Air VelocityDischarge Air Temp 28-32°Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


NS39VJL1CT– Service Lift GlassApplication:1234’ 6’ 8’ 12’Anti-Sweat Amps None None None NoneFan Amps .68 .68 1.02 1.36Light Amps .86 1.72 1.52 2.64Defrost Load Amps None None None None# Defrosts Required 1 1 1 1Evaporator Temperature °F +20° +20° +20° +20°BTU Requirements 1870 2550 3400 5100NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.There is .25 amps per lighted shelfDefrost Per Day Fail Safe TerminationOff Cycle 1 46 TIMEDischarge Air VelocityDischarge Air Temp 28-32Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


NS39VJL1– Service Lift GlassApplication:1244’ 6’ 8’ 12’Anti-Sweat Amps None None None NoneFan Amps .68 .68 1.02 1.36Light Amps .86 1.72 1.52 2.64Defrost Load Amps None None None None# Defrosts Required 1 1 1 1Evaporator Temperature °F +20° +20° +20° +20°BTU Requirements 1870 2550 3400 5100NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.There is .25 amps per lighted shelfDefrost Per Day Fail Safe TerminationOff Cycle 1 46 TIMEDischarge Air VelocityDischarge Air Temp 28-32°Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 2006


NS39VJ1– Service Curve GlassApplication:1254’ 6’ 8’ 12’Anti-Sweat Amps None None None NoneFan Amps .68 .68 1.02 1.36Light Amps .43 1.04 1.04 1.68Defrost Load Amps None None None None# Defrosts Required 1 1 1 1Evaporator Temperature °F +20° +20° +20° +20°BTU Requirements 1280 1920 2560 3840NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.There is .25 amps per lighted shelfDefrost Per Day Fail Safe TerminationOff Cycle 1 46 TIMEDischarge Air VelocityDischarge Air Temp 28-32°Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 06


NS39VJ1– Service Double CurveApplication:1264’ 6’ 8’ 12’Anti-Sweat Amps None None None NoneFan Amps .68 .68 1.02 1.36Light Amps .43 1.04 1.04 1.68Defrost Load Amps None None None None# Defrosts Required 1 1 1 1Evaporator Temperature °F +20° +20° +20° +20°BTU Requirements 1280 1920 2560 3840NOTE: For sizing conventional/individual condensing units ADD 8% to BTU LOAD.There is .25 amps per lighted shelfDefrost Per Day Fail Safe TerminationOff Cycle 1 46 TIMEDischarge Air VelocityDischarge Air Temp 28-32°Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths thatare UL and NSF approved.Issue: Sept - 2006


127RNW-950/RP Hot Food CaseCASE DATA 4’ 6’ 8’Number of Wells 3 5 7Number of lights 2 4 5Light Amps 230/1/60 2.6 8.7 10.9Cal-Rods 230/3/60 9.8 19.5 22.8Number of Fans 1 2 2Sweat Heaters 0 0 0Case is intended for use in an area where the environmental conditions arecontrolled and maintained such that conditions do not exceed 75 deg F and55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuous improvement,reserves the right to change at any time, specifications, design orprices without incurring obligation..Issue: March - 06


128NW-950/RP Hot Food CaseCASE DATA 4’ 6’ 8’Number of Wells 3 5 7Number of lights 2 4 5Light Amps 230/1/60 2.6 8.7 10.9Cal-Rods 230/3/60 9.8 19.5 22.8Number of Fans 1 2 2Sweat Heaters 0 0 0Case is intended for use in an area where the environmental conditions arecontrolled and maintained such that conditions do not exceed 75 deg F and55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuous improvement,reserves the right to change at any time, specifications, design orprices without incurring obligation.Issue: March - 06


129RNWB-950/RP Hot Food CaseCASE DATA 4’ 6’ 8’Number of Wells 3 5 7Number of lights 2 4 5Light Amps 230/1/60 2.6 8.7 10.9Cal-Rods 230/3/60 9.8 19.5 22.8Number of Fans 1 2 2Sweat Heaters 0 0 0Case is intended for use in an area where the environmental conditions arecontrolled and maintained such that conditions do not exceed 75 deg F and55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuous improvement,reserves the right to change at any time, specifications, design orprices without incurring obligation.Issue: March - 06


130S39NW-950 Hot Food CaseCASE DATA 4’ 6’ 8’Number of Wells 3 5 7Number of lights 2 4 5Light Amps 230/1/60 2.6 8.7 10.9Cal-Rods 230/3/60 9.8 19.5 22.8Number of Fans 1 2 2Sweat Heaters 0 0 0Case is intended for use in an area where the environmental conditions arecontrolled and maintained such that conditions do not exceed 75 deg F and55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuous improvement,reserves the right to change at any time, specifications, design orprices without incurring obligation.Issue: March - 06


Other Cases131


D6SC(1)(3)– Multi-DeckApplication:132CASE DATA 04’ 06’ 08’ 12’Power Supply 208V / 115V 208V / 115V 208V / 115V 208V / 115VFan Amps (Standard) 0.52 1.04 1.04 2.08Light Amp (2row canopy/ 4shelves) 1.5 2.4 3.0 4.8Drain Pan Heater 7.2 7.2 14.4 14.4Compressor RLA 6.9 6.9 13.8 13.8Condenser Fan Motor Amps 0.4 0.8 0.8 1.6Minimum Circuit Ampacity 17.7A 19.0A 2 x (17.7A) 2 x (19.0A)Maximum OCP 20A 20A 2 x 20A 2 x 20A# Defrosts Required 4 444Evaporator Temperature °F +20° +20° +20° +20°Refrigerant R-22 R-22 R-22 R-22BTU Requirements 6000 9000 1200018000Defrost Per Day Fail Safe TerminationOff Cycle 4 35min 43°Type I refrigerator, intended for use in an area where the environmentalconditions are controlled and maintained such that conditionsdo not exceed 75 deg F and 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>,whose policy is one of continuous improvement, reserves the right tochange at any time, specifications, design or prices without incurringobligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: March - 06


C1NVI1-SC– IslandApplication:133CASE DATA 08’ 12’Power Supply230V / 115V 230V / 115VAnti-Sweat Amps 1.81 2.23Fan Amps 1.22 1.22Light Amp N/A N/AMinimum Circuit Ampacity 14.7A 23.8AMaximum OCP 20A 40A# Defrosts Required 4 4Defrost Load Amps (If elec-230V) 11.30 14.80Evaporator Temperature °F +20° +20°Refrigerant R-22 R-22Average Product 45 45BTU Requirements 8800 13200Horse Power 2 2 x 2hpDefrost Per Day Fail Safe TerminationOff Cycle 4 30 min 48°Electric 4 40 min 55°Type I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.Issue: March - 06


S1VC1 – Self-ContainedApplication:134CASE DATA 04Power Supply115VAnti-Sweat Amps 0.1Fan Amps 0.7Light Amps 0.5Min Circuit Amp 21.4Max OCP 30Compressor Amps 9.7Ref. Cycle Amps 19.0Defrost Cycle Amps 9.3RefrigerantR-404AHorse Power 1/2CondensingUnitAll electrical data based on 115V and unlighted shelves. Forlighted shelves, please add 98 BTU and .25 amps per shelf.Defrost Per Day Fail Safe TerminationOff Cycle 4-6 40 min 45°Discharge Air Velocity FPMDischarge Air Temp °FType I refrigerator, intended for use in an area where the environmental conditionsare controlled and maintained such that conditions do not exceed 75 deg Fand 55% relative humidity. <strong>Kysor</strong>//<strong>Warren</strong>, whose policy is one of continuousimprovement, reserves the right to change at any time, specifications, design orprices without incurring obligation.Dual-Jet and Air Defrost are registered trademarks of <strong>Kysor</strong>//<strong>Warren</strong>.The above case model, has case lengths that are UL approved.Issue: May - 06 REV060824


Self-ContainedCase ComparisonApplication:135Model Number QM1AG3SC-8 VPA-1250-12RP-8Usage S/C Spot Merch. S/C Spot Merch.DESCRIPTION <strong>Kysor</strong>//<strong>Warren</strong> <strong>Kysor</strong>//<strong>Warren</strong>Product storage types Meat, Deli, Bkry Deli, BkryMerchandising Surface Area 20.6 26.77Merchandising Cubic Feet 13.9 10.69Height Overall 37.5” 37”Width Overall 42.0 53.75Length Overall 8”3” 8’2”Interior Width 31.75” 40”Interior Height Open Top Open TopSolid Front Option Option N/AGlass Front Option Standard StandardVoltage 120V—2 circuit 120V, 1ph# of wires 6 (2 hot, 2 neut, 2 gnd) 3 (1 hot, 1 neut, 1 gnd)Minimum circuit amps CKT#1:(9.38) / #2:(14.4)Max Breaker or Fuse size 20A per circuit 25ARefrigerant R-22 R-22QM1AG3-8Issue: March - 06