Instructions for the installer3.10 - DETERMINATION OF PRIMARY BOILER PUMP OR BOILER SYSTEM PUMPThe boiler pump must have a delivery head which can ensurethe water flow rate as shown in the diagram “<strong>Water</strong> pressurelosses”.The following table gives an indication of the pump’s flow ratein function of the Δt of the primary circuit if the installation hasa mixing headerSize of the pumpsIf determined by the installeror technical engineers mustbe sized according to thedata of boiler and system.Power supply in btu (kW)Max flow ratedemanded in gal/h (l/h) ΔT 27°F (15°C)Max flow ratedemanded in gal/h (l/h) ΔT 36°F (20°C)ALKON 90298,600(87,51)13261097In case of fixed raet pump isrecommended to choose acirculator with flow rate andhead at about 2/3 of thecharacteristic curve.The Δt between supply andreturn boiler should never beless than 27 °F (15 K).PRESSURE AVAIBLE TO THE SYSTEMPressure losses in wcQ: water flow rate gal/hNOTE: The use of a mixing header fitted between the boiler circuit and the system circuit is always advisable.It becomes INDISPENSABLE if the system requires flow rates superior to the maximum permitted boiler flowrates, which is to say lower than 27 °F (15 K).21