Instructions for the installer4.5 - VISUAL INSPECTION OF THE FLAME(2 and 4 year maintenance)The burner must flame evenly over the entire surface whenoperating correctly. The flame must burn with a clear, ORAN-GE, stable flame.SATISFACTORYCheck the flame through the inspection glassThe flame pattern should be as shown in the figures below.ORANGE FLAMEFLAME:YELLOW = CO2 HIGH NOT SATISFACTORYBLUE = CO2 LOW NOT SATISFACTORYORANGE = OK SATISFACTORY4.6 - PROPER REASSEMBLY ANDRESEALING OF THE VENT-AIRINTAKE SYSTEMAfter removing, inspected and possibly cleaned, Flue pipesand air intake, replace the tubes correctly.AAttention to the sense of double lip seals.ADOUBLE LIP SEAL43