Table 3-5. %Q Discrete Command Bit Definitions<br />
Bit Command Bit Command<br />
1 CH #1 Auto/Manual Mode 13 CH #7 Auto/Manual Mode<br />
2 CH #1 Enable/Disable Output 14 CH #7 Enable/Disable Output<br />
3 CH #2 Auto/Manual Mode 15 CH #8 Auto/Manual Mode<br />
4 CH #2 Enable/Disable Output 16 CH #8 Enable/Disable Output<br />
5 CH #3 Auto/Manual Mode 17 Spare<br />
6 CH #3 Enable/Disable Output 18 Spare<br />
7 CH #4 Auto/Manual Mode 19 Autotuning Method<br />
8 CH #4 Enable/Disable Output 20 Do Autotuning<br />
9 CH #5 Auto/Manual Mode 21 Spare<br />
10 CH #5 Enable/Disable Output 22 Disable Calibration Mode<br />
11 CH #6 Auto/Manual Mode 23 Spare<br />
12 CH #6 Enable/Disable Output 24 Spare (Cancel Autotuning)<br />
Channel #n Auto/Manual Mode: When this bit is set the channel #n closed-loop control<br />
procedure will be activated. The temperature will be controlled per the Set-Point. When this bit is<br />
set to ‘0’, the output will operate with a period and duty-cycle as specified by the corresponding<br />
parameters .<br />
Channel #n Enable/Disable Output: This bit enables output driver for channel #n. When this<br />
bit is cleared, the channel #n output will be disabled.<br />
Autotuning Method: When the TCM unit is to perform the autotuning procedure, this bit<br />
indicates which of two possible autotuning methods will be used. If the bit is set, the step<br />
response method will be used (suitable for situations where there is interference between zones)<br />
otherwise the relay response autotuning method will be used (suitable for zones that operate<br />
completely independent of each other).<br />
Do Autotuning: This bit commands the TCM unit to perform the autotuning process (see Figure<br />
3-1). When the TCM is commanded to do an Autotuning sequence (%Q reference + 20 is set) the<br />
recommended new parameters are multiplexed back to the PLC in register %AI reference +21 to<br />
%AI reference +27. This information should be validated by the user and then sent back to the<br />
TCM if parameters are acceptable. The TCM does not store the parameters automatically, it<br />
requires the PLC to send the new parameters. This ensures that the new values will be<br />
validated by the user<br />
Before the user sets this bit, the following settings should be prepared:<br />
• Required autotuning method set up (%Q reference +19)<br />
• The channels which will not be used must be inactive or must have disabled outputs.<br />
• The tuned channels must be active with the enabled outputs in the MANUAL mode.<br />
• A non-zero setpoint temperature must be set for each channel that will be tuned.<br />
• Only channels which do not exhibit any thermocouple error will be tuned.<br />