Chapter<br />

4<br />

Operation and Field Wiring Information<br />

This chapter is divided into two sections:<br />

Section 1: Principles of Operation for the Temperature Controller<br />

Section 2: Field Wiring Information<br />

Section 1: Principles of Operation<br />

Temperature Control<br />

PID Control Parameters<br />

Each zone receives a set of PID parameters from the Series 90-30 CPU for closed-loop control.<br />

Individual parameter action (proportional, integral, derivative) for each zone can be disabled by<br />

setting the parameter to 0.<br />

Operating Temperature Setpoint<br />

Temperature Tolerance Bands<br />

For each zone, an operating temperature setpoint from 0°C to 450°C for J and L thermocouples,<br />

or from 0°C to 600°C for K thermocouples can be set. The temperature is given in 0.1°C<br />

increments.<br />

For each zone, two temperature tolerance bands, labeled deviation and alarm, can be preset above<br />

and below the temperature setpoint. Each zone temperature regulator operates within these<br />

bands. The band temperature range extends from 0°C to 450°C (600 °C), given in 0.1°C<br />

increments. With these two tolerance bands the following conditions can be checked:<br />

GFK-1466 4-1