12.07.2015 Views

Concentrated Solar Power, Getting to the heart of energy - LEONI

Concentrated Solar Power, Getting to the heart of energy - LEONI

Concentrated Solar Power, Getting to the heart of energy - LEONI

SHOW MORE
SHOW LESS
  • No tags were found...

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

www.leoni-communication-infrastructure.comICON Instrumentation Cables19Electrical Properties at 20 °CConduc<strong>to</strong>r: nom. 1 mm²Conduc<strong>to</strong>r resistance: max. 18,5 Ω/kmInsulation resistance: min. 5000 MΩ × kmMutual capacitance: max. 150 nF/kmInductance: max. 1 mH/kmL/R Ratio: max. 25 µH/ΩTest voltage U rms(core : core):Test voltage U rms(core : screen):Operating voltage:1500 V1500 V300 VGeometrical dataNo. <strong>of</strong> elements RT <strong>of</strong> insulation RT <strong>of</strong> outer sheath Outer dia. Weightnom. nom. approx. approx.1 mm²/7 (mm) (mm) (mm) (kg/km)2 0.40 1.0 10.4 1194 0.40 1.1 12.3 1806 0.40 1.2 14.9 26610 0.40 1.3 18.2 401RT = Radial ThicknessRE = Instrumentation2X = XLPE Insulation(St) = Collective ScreenH = LSZH Outer sheathPiMF = Pair in Metal Foil

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!