You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
3. Cooling/heating capacity characteristics1. Cooling capacity calculation method :Required cooling capacity = Cooling capacity x Factor (, , , , * 1 ) kW <strong>Indoor</strong> air wet bulb temperature vs. capacity correction valueCapacity correction value1.21.11.00.90.81520 24<strong>Indoor</strong> air wet bulb temp. (˚C) Outdoor air dry bulb temperature vs.capacity correction valueCapacity correction value1.21.11.00.9–5 0 5 10 15 20 25 30 35 40 43Outdoor air dry bulb temp. (˚C) Air flow variation ratio of indoor unit vs. capacity correction (For concealed duct type only)Capacity correction value1.11.00.980 90 100 110 120Air flow variation ratio (%)*1 : Coefficient to use for correction of outdoor unit capacity when total capacity of the indoorunits are not equal to the outdoor unit capacity.15