You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
6. System Wiring DesignPower supply3 phase 380-415V 50HzEarth leakage breakerPower swithOutdoor unitEarthterminalU1 U2EarthterminalEarthU3 U4 U5 U6 terminalCentral remotecontrollerSingle phase220-240V 50HzOutdoor sideU1/U3U2/U4<strong>Indoor</strong> side<strong>Indoor</strong> unitRemotecontroller<strong>Indoor</strong> unitRemotecontroller<strong>Indoor</strong> unitRemotecontrollerU1/U2ABABU1/U2ABABU1/U2ABABLEarth terminalNControlwiringFS unitCN02LEarth terminalNCN81ControlwiringFS unitCN02LEarth terminalNControlwiringFS unitCN02Power supplySingle phase220-240V50Hz Earth leakagebreakerPower switchPullBoxEarthterminalPowerlineCN01EarthterminalPullBoxEarthterminalPowerlineCN01EarthterminalEarthterminalPowerlineCN01EarthterminalNOTE :Control wire and power line wire between FS unit and indoor unit are the accessary parts of FS unit. (Wire length : 6m)If the length between indoor and FS unit exceeds 5m, connect by using the connection cable kit sold separately (RBC-CBK15FE).7. Design• Outdoor unit50HzModel nameMMY-VoltageCompressor Fan Motor Power SupplyRangeMin Max RLA LRA kW FLA MCA MOCP ICFMAP0801FT8 342 457 5.2 + 5.2 — 0.60 1.0 20.0 30 —MAP1001FT8 342 457 6.5 + 6.5 — 0.60 1.1 22.5 30 —MAP1201FT8 342 457 9.5 + 9.5 — 0.60 1.1 24.5 30 —LegendMCAMOCPICFRLA: Minimum Circuit Amps: Maximum Overcurrent Protection (Amps): Maximum Instantaneous Current Flow Start: Rated Load AmpsLRAFLAkW: Locked Rotor Amps: Full Load Amps: Fan Motor Rated Output (kW)NOTE :RLA is based on the following conditions.<strong>Indoor</strong> temperature: 27°C DB/19°C WBOutdoor temperature: 35°C DB30