Water/Glycol-Cooled Systems—Standard and Optional Features6.6 Glycol-Cooled Systems—Optional Heat Rejection Devices for Self-Contained andSplit Systems6.6.1 Dual Pump PackageThe dual pump package features two full size glycol pumps, each capable of providing sufficient flowfor system operation. A flow switch will sense the loss of flow, should the lead pump fail, andautomatically command the standby pump to start. The complete system includes dual pumphousing, pumps, lead-lag switch and flow switch (for field installation). The dual pump packageprovides redundancy, protecting against costly downtime in the computer room.6.6.2 <strong>Liebert</strong> Quiet-Line Drycoolers<strong>Liebert</strong> Quiet-Line Drycoolers can help your facility meet the strictest noise codes, and do so at lesscost than traditional drycoolers <strong>with</strong> acoustical shielding.14