Dimensional DrawingsFigure 14Cabinet and floor planning dimensions—Downflow (BF/BE) models30-1/2"(775mm)32-1/2"(826mm)OverallDimension32-1/2"(826mm)OverallDimensionProjection of DisplayBezel 5/8" (16mm)30-1/2"(775mm)Optional 1-5/8" (41mm)Flange for Duct orPlenum Connection76"(1930mm)1" (25mm) FRONT & SIDES3/4" (19mm) REARShaded area indicatesa recommended clearance of34” (864mm) for componentaccess. Right side accesssuggested for GLYCOOL units1"(25.4mm)30-1/2"(775mm)30-1/2"(775mm)1"(25.4mm)9"(229mm)1" (25.4mm)Standard Electrical LocationStandard Piping LocationFloor Level12"4"(305mm)(102mm)30-1/2"(775mm)8"(203mm)1"(25.4mm)30-1/2"(775mm)FLOOR CUTOUT DIMENSIONS28-1/2"(724mm)30-1/2"(775mm)30-1/2"(775mm)1"(25.4mm)50HzModelsUnit Weight60HzModelslb (kg)BF035E BF036E 535 (243)BF059E BF060E 545 (247)BF040A BF042A 615 (279)BF065A BF067A 670 (304)BF045WG BF046WG 700 (318)BF070WG BF071WG 750 (340)BF072C BF068C 545 (247)BF101C BF102C 555 (252)BE058G BE061G 785 (356)See SpecificationSheet for Floor StandHeight Ordered.OPTIONAL FLOOR STAND DIMENSIONAL DATADPN000351Rev. 0137