Electrical Data—60HzTable 16 Fan speed control condensers95°F (35°C) Ambient (1 Phase - 60Hz)DCSF083/DCSF104Voltage 208/230 460 575FLA 4.8 2.5 1.9WSA 6.0 3.1 2.4OPD 15.0 15.0 15.0Table 17 <strong>Liebert</strong> Lee-Temp condensers95°F (35°C) Ambient (3 Phase - 60Hz)DCSL083/DCSL104Voltage 208/230 460 575FLA 3.5 1.7 1.4WSA 4.4 2.1 1.8OPD 15.0 15.0 15.0Table 18 VFD-controlled condenser95°F (35°C) Ambient (3 Phase - 60Hz)TCSV083/TCSV104Voltage 208/230 460FLA 3.7 1.8WSA 4.6 2.3OPD 15 15Table 19 <strong>Liebert</strong> Lee-Temp receiver heater pads for use w/DCSL condensersVolts 120 230Watts/Pad 150 150FLA 1.4 0.7WSA 1.8 0.9OPD 15 15Separate electrical source required for continuous operation of single phase heater pads for <strong>Liebert</strong> Lee-Temp.48