4.9 RESCUE AND FIRE FIGHTING SERVICES<br />
The level of protection for rescue and fire fighting is determined based on the<br />
dimensions of aircraft using the airport in accordance with “<strong>Airport</strong> Service Manual Part<br />
I - Rescue and Fire Fighting” (ICAO). The category for A320 design aircraft is 6. The<br />
minimum usable amounts of extinguishing agents and fire fighting vehicles required for<br />
category 6 are as follows:<br />
Table 4.9-1 Minimum Usable Amount of Extinguishing Agents & Fire Fighting Vehicles<br />
Requirements for Category 6<br />
Min. Number of Rescue and Fire Fighting Vehicles 2<br />
Min Storage of Extinguishing Agents<br />
Water (liters)<br />
11,800<br />
Discharge Rate (Foam Solution/min)<br />
6,000<br />
Complementary Agents<br />
Dry Chemical Powder (kgs.)<br />
225<br />
4.10 AIRPORT UTILITIES<br />
The demand for airport utilities is estimated based on the average unit demands of<br />
airports and summarized in Table 4.10-1.<br />
Table 4.10-1 Unit Demand for Utilities for Planning Purposes<br />
Utilities Area of Application Unit Demand<br />
Water and<br />
Sewage<br />
Passenger Terminal Building<br />
Cargo Terminal Building<br />
Administration Building and Other Buildings<br />
23 liters/sq.m./day<br />
3 liters/sq.m./day<br />
10 liters/sq.m./day<br />
Passenger Terminal Building 0.07 kgs/sq.m./day<br />
Solid Waste Cargo Terminal Building 0.14 kgs/sq.m./day<br />
Administration Building and Other Buildings 0.14 kgs/sq.m./day<br />
Passenger Terminal Building 100 VA/sq.m.<br />
Electricity Cargo Terminal Building 60 VA/sq.m.<br />
Administration Building and Other Buildings 80 VA/sq.m.<br />
Passenger Terminal Building 0.005 extension/sq.m.<br />
Telephone<br />
Cargo Terminal Building<br />
Administration Building and Other Buildings<br />
0.005 extension/sq.m.<br />
0.025 extension/sq.m<br />
Trunk Lines<br />
25 lines<br />
Basis : Average Unit Demand from Mactan, Manila and Narita <strong>Airport</strong>s<br />
Note: Generated Sewage is assumed at 100 % of Water Consumption<br />
Secondary power supply will be estimated to provide emergency power to essential<br />
facilities and equipment at the airport to maintain operation during power failure.<br />
4-14