2.1.6.3 Side Support<br />

The minimum side support required for <strong>Supercrete</strong><br />

<strong>Structural</strong> <strong>Floor</strong> <strong>Panels</strong> is 50mm. If the side support is from<br />

a bond beam formed with <strong>Supercrete</strong> Facing Blocks on<br />

top of a <strong>Supercrete</strong> Block wall, the panel should not rest<br />

only on the 50mm width of the facing block as there is a<br />

likelihood of the facing block debonding from the poured<br />

Block to <strong>Structural</strong> <strong>Floor</strong> Panel side support<br />

Detail No. SFP 2-8<br />

Ring anchor reinforcement<br />

in grout fill Selected floor finish<br />

150, 175, 200, 225<br />

or 250mm<br />

<strong>Supercrete</strong><br />

<strong>Structural</strong> <strong>Floor</strong><br />

<strong>Panels</strong><br />

Ceiling hangers<br />

Ceiling battens<br />

Suspended<br />

Ceiling<br />

Supercoat Coating System<br />

Cast insitu bond beam ring anchor<br />

concrete behind. In this case, the poured concrete should<br />

be continued right up to the inside face of the wall, or, if the<br />

wall is wide enough, the panel should have 50mm of edge<br />

bearing support on the bond beam poured concrete as per<br />

bond beam Type 9 (see Figure 1, page 23).<br />

Interior lining Supercoat Coating System or plasterboard linings<br />

Thick bed mortar joint raked out for sealant at coating junction<br />

Minimum for panel<br />

side support<br />

Optional scotia<br />

Internal linings<br />

Exterior <strong>Supercrete</strong><br />

Block wall 200mm min, 250, or<br />

300mm blocks<br />

Panel sides supported on Type 2 bond beam. Note the threaded hangers ready to<br />

take the suspended ceiling grid.<br />

SFP 2012 24 Copyright © <strong>Supercrete</strong> Limited 2008<br />