When installing on "drawer"-type units, ensure<br />
that the electrical connections are long enough<br />
to enable the units to be pulled out.<br />
If a water-filled cooling coil is installed upstream<br />
of the first heat exchanger, then the frost protection<br />
thermostat must be installed upstream of<br />
the cooling coil, in the direction of the air flow.<br />
With large heat exchangers, or with heat<br />
exchangers comprising several units, more<br />
than one frost thermostat must be installed<br />
(minimum 1 per unit).<br />
Temperature · Frost protection<br />