Flow velocity · Air<br />
54<br />
Flow velocity Air<br />
Formula:<br />
dg = Equivalent diameter<br />
The pressure-tapping point must not be located<br />
in turbulent air. Ensure sufficiently long settling-zones<br />
upstream and downstream of the<br />
tapping point.<br />
A settling-zone consists of a straight section of<br />
pipe or duct, with no obstructions.<br />
Fan-belt monitoring<br />
The differential pressure across the fan is only<br />
suitable for fan-belt monitoring.<br />
■ Negative connection (–) on suction side<br />
use copper tube<br />
■ Positive connection (+) on discharge side:<br />
use Pitot tube<br />
Flow monitoring<br />
Flow detectors (electrothermal)<br />
Electrothermal flow detectors must be installed<br />
in a zone with a high flow velocity, e.g. where<br />
pipes narrow.<br />
Differential pressure<br />
Do not monitor flow or differential pressure<br />
where flow resistance is variable, e.g. at filters,<br />
cooling coils, fans etc. Suitable locations:<br />
heating coils, silencers, baffles, attenuators.