Pressure control in VAV systems<br />

The sensing point must be sited at the most remote point in the duct<br />

system. In duct systems with a large number of branches, the use of several<br />

sensing points is recommended (the lowest pressure is used for control).<br />

If some parts of the ductwork (zones) are shut off by dampers, the relevant<br />

sensors must be disconnected.<br />

The setpoint can only be maintained at the sensing point.<br />

Practical tips<br />

87