Pressure control in VAV systems<br />
The sensing point must be sited at the most remote point in the duct<br />
system. In duct systems with a large number of branches, the use of several<br />
sensing points is recommended (the lowest pressure is used for control).<br />
If some parts of the ductwork (zones) are shut off by dampers, the relevant<br />
sensors must be disconnected.<br />
The setpoint can only be maintained at the sensing point.<br />
Practical tips<br />
87