Sensor Installation Handbook Preface 3rd edition - Siemens ...
Sensor Installation Handbook Preface 3rd edition - Siemens ...
Sensor Installation Handbook Preface 3rd edition - Siemens ...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Pressure Liquids<br />
Pressure tapping point:<br />
Sensing hole: diameter 5 mm, drilled and<br />
deburred.<br />
Smooth interior (no burrs).<br />
Use a damping coil to avoid transferring vibra -<br />
tions. Bend a 1 m long copper pipe, 4…6 mm in<br />
diameter, into a spiral with loops with a diameter<br />
of 15 cm.<br />
Wrong:<br />
Air bubbles and condensate remain trapped.<br />
Pressure · Liquids<br />
51