Principles of operation<br />

64<br />

Switching devices<br />

On/off<br />

Changeover<br />

3-position<br />

Multi-stage<br />

Dynamic switching differential<br />

Setpoint<br />

Switching devices<br />

Thermostats<br />

Hygrostats<br />

Pressure switches<br />

Where a switching device such as a thermostat is installed in a system,<br />

it should be noted that the temperature swing will be wider than the<br />

switching differential of the thermostat. The thermostat operates at the<br />

switching points specified in the data sheet (static switching differential),<br />

but the inertia of the system (residual heat, dead time etc.) causes the controlled<br />

variable to overshoot or undershoot. The finally measurable temperature<br />

swing (the dynamic switching differential) will therefore always be<br />

wider than the static switching differential of the thermostat.