Calibration<br />

82<br />

Clinical syringe<br />

∅p filter<br />

Calibrating a filter monitor<br />

Use a clinical syringe to check the filter monitor as follows:<br />

Method:<br />

■ Switch off the system.<br />

■ Disconnect the differential pressure tubes (+ and –) from the<br />

pressure-tapping points.<br />

Connect the syringe and a manometer (U-tube) to the “+” side.<br />

■ Switch on the system.<br />

■ Gradually increase the pressure with the syringe until the manometer<br />

shows that the switching point has been reached.<br />

■ The alarm device should trip at this point. (Recalibrate if necessary.)<br />

■ Switch off the system.<br />

■ Re-connect the differential pressure tubes.<br />

■ Switch on the plant again.