Calibration<br />
82<br />
Clinical syringe<br />
∅p filter<br />
Calibrating a filter monitor<br />
Use a clinical syringe to check the filter monitor as follows:<br />
Method:<br />
■ Switch off the system.<br />
■ Disconnect the differential pressure tubes (+ and –) from the<br />
pressure-tapping points.<br />
Connect the syringe and a manometer (U-tube) to the “+” side.<br />
■ Switch on the system.<br />
■ Gradually increase the pressure with the syringe until the manometer<br />
shows that the switching point has been reached.<br />
■ The alarm device should trip at this point. (Recalibrate if necessary.)<br />
■ Switch off the system.<br />
■ Re-connect the differential pressure tubes.<br />
■ Switch on the plant again.