Preventive frost protection thermostat:<br />

The preventive frost protection thermostat operates in two phases.<br />

Frost alarm<br />

Open<br />

Closed<br />

Valve<br />

Temperature<br />

Example:<br />

1. If the air temperature around the frost thermostat drops below 6 °C, the<br />

thermostat takes over control of the heat exchanger valve to maintain<br />

the air temperature at a value between 2 °C and 6 °C.<br />

2. If the air temperature is still below the 2 °C switch-off point, (e.g. due to<br />

insufficient heating), the frost alarm will trip.<br />