CONSTANT PRESSURE CONTROL<br />
Leave one of the pressure taps<br />
unconnected.<br />
CONSTANT AIRFLOW CONTROL<br />
Connect the two taps and enter the value K shown in the<br />
table above into the pressure transducer.<br />
ENGLISH<br />
Air<br />
direction<br />
Important: the upper pressure tube must be connected to the “+” terminal and the lower one<br />
to the “-“ terminal. Failing this, the pressure measured will be out of range and the transmitter<br />
screen will flash.<br />
6.7.2.2.1 TDP-S Mo<strong>de</strong>l<br />