• We suggest having all the elements nee<strong>de</strong>d for the installation on hand, mentioning the<br />
following <strong>de</strong>vices in particular:<br />
- Unit intake pre-filter that traps suspen<strong>de</strong>d particulate matter.<br />
- Bleed valves should be fitted at each of the high points in the installation to maintain<br />
good water circulation.<br />
- It is recommen<strong>de</strong>d to keep water in the hydraulic system at all times (install an<br />
auto-filler valve and pressure switches that send an alarm and shut off power to<br />
the equipment, etc.)<br />
- Check to make sure that the flow of water circulating through the unit is appropriate.<br />
- Shut-off valves must be installed at each connection on the water line to allow the<br />
unit to be isolated if necessary (to clean filters, make repairs, replace parts etc.) and<br />
avoid the need to completely drain the water circuit.<br />
- Anti-vibration bellows should be installed at the inlet and outlet from the unit to<br />
prevent the transmission of vibrations that could result in damage to the heat exchanger<br />
coils due to excess stress on the circuits.<br />
ENGLISH<br />
6.9. CONNECTING THE UNIT TO THE DUCT SYSTEM<br />
• Never use the unit as a support or weight-bearing structure for ductwork.<br />
• Connect the unit to the air ducts using flexible connectors to prevent vibrations from being<br />
transmitted to the duct system.<br />
• Check to make sure air intake and flow are not being blocked and that there are no obstacles<br />
impeding good air circulation. Failure to do so will affect the efficiency of the system.<br />
6.10. DRAINAGE SYSTEM<br />
• A siphon must be installed with pressure head difference in mmWG greater than the pressure<br />
provi<strong>de</strong>d by the fan, to facilitate draining con<strong>de</strong>nsate from the tray.<br />
• The drainage system should have a minimum slope of 2%.<br />