Constant pressure operation<br />

• Check that the transmitter output signal type jumper (mA/V) in the voltage position (factory<br />

setting).<br />

• Configure the DIP switches as indicated in the tables below. The required pressure range is<br />

selected using the switches DIP1, DIP2 and DIP3.<br />

ENGLISH<br />

Pressure range (Pa) DIP 1 DIP 2 DIP 3<br />

-50...+50 1 1 1<br />

0...+100 0 1 1<br />

0...+150 1 0 1<br />

0...+300 0 0 1<br />

0...+500 1 1 0<br />

0...+1000 0 1 0<br />

0...+1600 1 0 0<br />

0...+2500 0 0 0<br />

DIP switch DIP 4/5/6 ON / OFF Notes<br />

DIP 4 - Not used<br />

DIP 5<br />

Select according to the required damping<br />

time: 0,4s (OFF) / 10s (ON))<br />

DIP 6 OFF Minimum output voltage 0V<br />

6.7.2.2.2 TDP-D Mo<strong>de</strong>l<br />

52