Steps to follow in the event of a fault on the frequency inverter:<br />

To avoid possible injury to personnel, the inverter has to be reset manually. In the event of a<br />

fault, proceed as <strong>de</strong>scribed below:<br />

• Disconnect the inverter from the power supply<br />

• Solve the problem<br />

• Reconnect the power supply (the inverter will start up automatically)<br />

6.7.2.3.3 Reconfiguring the frequency inverter<br />

ENGLISH<br />

In the event that configuration settings are lost due to a frequency inverter fault, proceed as<br />

<strong>de</strong>scribed below.<br />

Firstly enter programming mo<strong>de</strong>. The inverter has two operating mo<strong>de</strong>s, RUN and PRO-<br />

GRAMMING. To move from one to the other, press ESC for two seconds.<br />

• Press ESC for two seconds until the mo<strong>de</strong> indicator LEDs flash simultaneously.<br />

Next unlock the inverter:<br />

• Press “ENT” and turn the wheel until you reach the “SUP-“menu<br />

• Press “ENT” and turn the wheel until you reach the “COd” parameter<br />

• Press “ENT” and turn the wheel until “1951” appears<br />

• Press “ENT” and turn the wheel until “OFF” appears<br />

• Press “ENT” and return to the main menu by pressing “ESC” twice<br />

Reset to factory configuration:<br />

• Go to the “drC” menu and press “ENT”<br />

• Move to “CFG” and press “ENT”<br />

• Select “Std” and press “ENT”<br />

• Press “ESC” to exit and use the wheel to move to “FCS”<br />

• Press “ENT” and move to “In1”<br />

• Press “ENT” and the inverter will be reset to the factory configuration<br />

Proceed to reconfigure the frequency inverter. To do this, set the parameters in the table<br />

below:<br />

Menu Parameter Value<br />

CtL LAC L3<br />

CtL Fr1 AI1<br />

CtL Fr2 AIU1<br />

CtL rFC LI3<br />

FLt Atr nO<br />

FLt FLr YES<br />

FLt EtF LI5<br />

FLt LEt LO<br />

drC tUn YES<br />

drC UFt nLd<br />